Chapter 9
162
Logic programming – Function blocks
9.8.7
EDM (External device monitoring)
Function block diagram
General description
The EDM (External device monitoring) function block allows to control an external
device (e.g. a contactor) and to check on the basis of its feedback signal whether it
has switched as expected. To this purpose the external device is connected to
Output
1
and/or
Output 2
. The feedback signal is connected to the
EDM feedback
input. The
Monitored input
is connected to the logic signal that represents the desired state for
the external device, e.g. the
Enable
output of a Reset function block.
Parameters of the function block
Parameter
Possible values
Max. feedback delay
100 to 1,000 ms in 10 ms steps. The value has to be greater than
the logic execution time.
Use fault present
With
Without
Use Error reset
Output 1 and Output 2
Both outputs have always the same value. This way, two outputs are available to
connect two output elements directly.
Output 1
and
Output 2
become High, if the
EDM feedback
is High and the
Monitored input
changes from Low to High subsequently.
Output 1
and
Output 2
become Low, if the
Monitored input
is Low or if an EDM
error is present (
EDM error
output is High).
EDM error and Fault present
Generally it is expected that the
EDM feedback
input always takes the inverted value
of the
Monitored input
before the configured
Max. feedback delay
(T
EDM
) has
expired.
The
EDM error
and
Fault present
outputs become High, if …
the
Monitored input
changes from Low to High and the
EDM feedback
input is
Low (irrespective of T
EDM
), or
the
Monitored input
changes from Low to High and the
EDM feedback
input does
not change from High to Low before T
EDM
has expired, or
the
Monitored input
changes from High to Low and the
EDM feedback
input does
not change from Low to High before T
EDM
has expired, or
the
Monitored input
is Low and the
EDM feedback
input changes to Low for
longer than T
EDM
, or
the
Monitored input
is High and the
EDM feedback
input changes to High for
longer than T
EDM
.
Figure 144:
Function block diagram for
the EDM function block
Table 69:
Parameters of the EDM
function block
Содержание SW1DNN-WS0ADR-B
Страница 2: ......
Страница 287: ...Chapter 15 284 Annex 15 Annex 15 1 Example application reports 15 1 1 Example application Newspaper palletizer ...
Страница 288: ...Chapter 15 285 Annex ...
Страница 289: ...Chapter 15 286 Annex ...
Страница 290: ...Chapter 15 287 Annex ...
Страница 291: ...Chapter 15 288 Annex ...
Страница 292: ...Chapter 15 289 Annex ...
Страница 293: ...Chapter 15 290 Annex ...
Страница 294: ...Chapter 15 291 Annex ...
Страница 295: ...Chapter 15 292 Annex ...
Страница 296: ...Chapter 15 293 Annex ...
Страница 297: ...Chapter 15 294 Annex ...
Страница 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Страница 299: ...Chapter 15 296 Annex ...
Страница 300: ...Chapter 15 297 Annex ...
Страница 301: ...Chapter 15 298 Annex ...
Страница 302: ...Chapter 15 299 Annex ...
Страница 303: ...Chapter 15 300 Annex ...
Страница 304: ...Chapter 15 301 Annex ...
Страница 305: ...Chapter 15 302 Annex ...
Страница 306: ...Chapter 15 303 Annex ...
Страница 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Страница 308: ...Chapter 15 305 Annex ...
Страница 309: ...Chapter 15 306 Annex ...
Страница 310: ...Chapter 15 307 Annex ...
Страница 311: ...Chapter 15 308 Annex ...
Страница 312: ...Chapter 15 309 Annex ...
Страница 313: ...Chapter 15 310 Annex ...
Страница 314: ...Chapter 15 311 Annex ...
Страница 316: ...Chapter 15 313 Annex 15 3 Precautions 1 Edit a CSV file exported from Setting and Monitoring tool in a text editor ...
Страница 321: ......