Chapter 9
203
Logic programming – Function blocks
In the hardware configuration the used inputs must be configured as single channel
signals, i.e. no dual channel input evaluation on the safety I/O module.
Parameters of the function block
Parameter
Possible values
Discrepancy time pair 1
0 = disabled, 10 to 500 ms in 10 ms steps. If enabled, the
value has to be greater than the logic execution time.
Discrepancy time pair 2
0 = disabled, 10 to 500 ms in 10 ms steps. If enabled, the
value has to be greater than the logic execution time.
Number of outputs
1 (Enable output)
2 (Enable output and Discrepancy error pair 1 output)
3 (Enable output, Discrepancy error pair 1 output and
Discrepancy error pair 2 output)
Use fault present
With
Without
The function block evaluates its input signals in pairs.
Input 1A
and
Input 1B
form a
dual-channel evaluation and have to be complementary.
Input 2A
and
Input 2B
form
a dual-channel evaluation and also have to be complementary. A discrepancy time
can be specified for each of both input pairs.
The synchronization time is the time during which the input pairs may have different
values. As specified in the standards and regulations, the synchronization time for a
two-hand switch evaluation may not exceed 500 ms (the synchronization time is
preset and cannot be changed).
For the behaviour of the double dual-channel evaluation see Section 9.9.2 and
Section 9.9.3.
The synchronization evaluation for the Two hand control type IIIC function block differs
from the Safety gate monitoring function block with regard to the condition for the
Inactive synchronization status. For the Two hand control type IIIC function block, both
dual-channel evaluations must be Inactive, i.e. the inputs A/B of both input pairs must
be Low/High at the same time.
Furthermore the Two hand control type IIIC function block has no
Synchronization
error
output, because with a two hand control it is not regarded as an error if not both
manual switches are actuated within the specified 500 ms. However this
synchronization time may not be exceeded, because otherwise the
Enable
output will
not change to High.
Sequence/timing diagram
Table 90:
Parameters of the Two-hand
control type IIIC function
block
Figure 193:
Sequence/timing diagram
for the Two hand control
type IIIC function block
Содержание SW1DNN-WS0ADR-B
Страница 2: ......
Страница 287: ...Chapter 15 284 Annex 15 Annex 15 1 Example application reports 15 1 1 Example application Newspaper palletizer ...
Страница 288: ...Chapter 15 285 Annex ...
Страница 289: ...Chapter 15 286 Annex ...
Страница 290: ...Chapter 15 287 Annex ...
Страница 291: ...Chapter 15 288 Annex ...
Страница 292: ...Chapter 15 289 Annex ...
Страница 293: ...Chapter 15 290 Annex ...
Страница 294: ...Chapter 15 291 Annex ...
Страница 295: ...Chapter 15 292 Annex ...
Страница 296: ...Chapter 15 293 Annex ...
Страница 297: ...Chapter 15 294 Annex ...
Страница 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Страница 299: ...Chapter 15 296 Annex ...
Страница 300: ...Chapter 15 297 Annex ...
Страница 301: ...Chapter 15 298 Annex ...
Страница 302: ...Chapter 15 299 Annex ...
Страница 303: ...Chapter 15 300 Annex ...
Страница 304: ...Chapter 15 301 Annex ...
Страница 305: ...Chapter 15 302 Annex ...
Страница 306: ...Chapter 15 303 Annex ...
Страница 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Страница 308: ...Chapter 15 305 Annex ...
Страница 309: ...Chapter 15 306 Annex ...
Страница 310: ...Chapter 15 307 Annex ...
Страница 311: ...Chapter 15 308 Annex ...
Страница 312: ...Chapter 15 309 Annex ...
Страница 313: ...Chapter 15 310 Annex ...
Страница 314: ...Chapter 15 311 Annex ...
Страница 316: ...Chapter 15 313 Annex 15 3 Precautions 1 Edit a CSV file exported from Setting and Monitoring tool in a text editor ...
Страница 321: ......