Chapter 9
164
Logic programming – Function blocks
Parameters of the function block
Parameter
Possible values
Reset condition
Manual
reset
Auto
reset
Continuous monitoring
when valve is active
No
Yes
Valve mode
Single (Control 1, Output 1a, Output 1b, Feedback 1
activated)
Double (Control 1, Output 1a, Output 1b, Feedback 1, Output
2a, Output 2b, Feedback 2 activated)
Directional (Control 1, Output 1a, Output 1b, Feedback 1,
Control 2, Output 2a, Output 2b, Feedback 2, Directional
error activated)
Max. switch-on feedback
delay time
50 ms to 10 s in steps of 10 ms (0 = disabled, only with CPU
firmware V2.00.0 or higher).
If this parameter is disabled, then the option Continuous
monitoring when valve is active has to be deactivated as well.
If this parameter is enabled, the value has to be greater than the
logic execution time.
Max. switch-off feedback
delay time
50 ms to 10 s in steps of 10 ms (0 = disabled, only with CPU
firmware V2.00.0 or higher).
If enabled, the value has to be greater than the logic execution
time.
Min. reset pulse time
100
ms
350
ms
Use fault present
With
Without
Connect the feedback signals correctly!
The signals for
Feedback 1
and
Feedback 2
have to be protected against short-
circuits to the signals for outputs (e.g.
Output 1a
,
1b
,
2a
and
2b
) as well as against
each other (e.g. by means of protected wiring or wiring of these signals solely within
the control cabinet).
Output 1a to Output 2b
Both outputs of a pair (
Output 1a
and
Output 1b
or
Output 2a
and
Output 2b
) have
always the same value. This way, two outputs per valve are available to connect two
output elements directly.
Output 1a/1b
or
Output 2a/2b
become High, if the related
Feedback 1
or
Feedback
2
input is High and the related
Control
input changes from Low to High subsequently.
Output 1a/1b
or
Output 2a/2b
become Low, if the related
Control
input is Low or if a
fault is present (
Feedback error
output is High or
Directional error
output is High).
The related control input for
Output 1a/1b
is always
Control 1
.
The related control input for
Output 2a/2b
depends on the configured valve type:
For Double valve:
Control 1
For Directional valve:
Control 2
Table 70:
Parameters of the Valve
monitoring function block
ATTENTION
Содержание SW1DNN-WS0ADR-B
Страница 2: ......
Страница 287: ...Chapter 15 284 Annex 15 Annex 15 1 Example application reports 15 1 1 Example application Newspaper palletizer ...
Страница 288: ...Chapter 15 285 Annex ...
Страница 289: ...Chapter 15 286 Annex ...
Страница 290: ...Chapter 15 287 Annex ...
Страница 291: ...Chapter 15 288 Annex ...
Страница 292: ...Chapter 15 289 Annex ...
Страница 293: ...Chapter 15 290 Annex ...
Страница 294: ...Chapter 15 291 Annex ...
Страница 295: ...Chapter 15 292 Annex ...
Страница 296: ...Chapter 15 293 Annex ...
Страница 297: ...Chapter 15 294 Annex ...
Страница 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Страница 299: ...Chapter 15 296 Annex ...
Страница 300: ...Chapter 15 297 Annex ...
Страница 301: ...Chapter 15 298 Annex ...
Страница 302: ...Chapter 15 299 Annex ...
Страница 303: ...Chapter 15 300 Annex ...
Страница 304: ...Chapter 15 301 Annex ...
Страница 305: ...Chapter 15 302 Annex ...
Страница 306: ...Chapter 15 303 Annex ...
Страница 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Страница 308: ...Chapter 15 305 Annex ...
Страница 309: ...Chapter 15 306 Annex ...
Страница 310: ...Chapter 15 307 Annex ...
Страница 311: ...Chapter 15 308 Annex ...
Страница 312: ...Chapter 15 309 Annex ...
Страница 313: ...Chapter 15 310 Annex ...
Страница 314: ...Chapter 15 311 Annex ...
Страница 316: ...Chapter 15 313 Annex 15 3 Precautions 1 Edit a CSV file exported from Setting and Monitoring tool in a text editor ...
Страница 321: ......