Chapter 9
231
Logic programming – Function blocks
In order to fulfill the safety standards it may be necessary to use tested switches for
the cam input signals, each with different test sources. To use different test sources
for the cam signals, the
Overrun cam
,
Upstroke cam
and
Dynamic cam
need to be
connected to different WS0-XTDI or WS0-XTIO modules.
One WS0-XTDI has two test sources only, even if it has eight test output terminals.
Overrun monitoring
The Eccentric press contact function block monitors the overrunning of the press. If
the
Overrun cam
is left although the press is supposed to have stopped, then the
function block detects an Overrun error.
The
Drive released
input signal must then accord to Figure 216 and the following rule.
At the
Drive released
input there has to be either a Low to High transition while the
Top
output is High or the
Drive released
input has to be High at the end of the
Overrun cam
(High-Low transition). If none of these two conditions is fulfilled, the
Enable
output becomes Low and the
Overrun error
output becomes High.
The
Drive released
input must be connected to the signal that controls the physical
output of the press drive, so that the function block can determine whether the press is
currently supposed to be running or has been stopped. Typically this is the
Enable
output of a subsequent Press setup or Press single stroke function block.
Do not connect any physical input signals to the
Drive released
input. Connect the
signal that controls the physical output for the press drive using a jump address or a
CPU marker.
If a jump address is used, make sure that this signal is a loop-back. This is
indicated by a clock icon on the destination tag of the jump address. To this
purpose, connect the outputs of this function block to the following function blocks
before you connect the jump address to the
Drive released
input. This applies
especially if all connections to the following function blocks are also realized using
jump addresses.
If a CPU marker is used, then a Routing function block must be used to split the
signal to the physical output for the press drive and to the CPU marker output.
Note
Figure 216:
Overrun monitoring with the
Eccentric press contact
function block
Note
Содержание SW1DNN-WS0ADR-B
Страница 2: ......
Страница 287: ...Chapter 15 284 Annex 15 Annex 15 1 Example application reports 15 1 1 Example application Newspaper palletizer ...
Страница 288: ...Chapter 15 285 Annex ...
Страница 289: ...Chapter 15 286 Annex ...
Страница 290: ...Chapter 15 287 Annex ...
Страница 291: ...Chapter 15 288 Annex ...
Страница 292: ...Chapter 15 289 Annex ...
Страница 293: ...Chapter 15 290 Annex ...
Страница 294: ...Chapter 15 291 Annex ...
Страница 295: ...Chapter 15 292 Annex ...
Страница 296: ...Chapter 15 293 Annex ...
Страница 297: ...Chapter 15 294 Annex ...
Страница 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Страница 299: ...Chapter 15 296 Annex ...
Страница 300: ...Chapter 15 297 Annex ...
Страница 301: ...Chapter 15 298 Annex ...
Страница 302: ...Chapter 15 299 Annex ...
Страница 303: ...Chapter 15 300 Annex ...
Страница 304: ...Chapter 15 301 Annex ...
Страница 305: ...Chapter 15 302 Annex ...
Страница 306: ...Chapter 15 303 Annex ...
Страница 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Страница 308: ...Chapter 15 305 Annex ...
Страница 309: ...Chapter 15 306 Annex ...
Страница 310: ...Chapter 15 307 Annex ...
Страница 311: ...Chapter 15 308 Annex ...
Страница 312: ...Chapter 15 309 Annex ...
Страница 313: ...Chapter 15 310 Annex ...
Страница 314: ...Chapter 15 311 Annex ...
Страница 316: ...Chapter 15 313 Annex 15 3 Precautions 1 Edit a CSV file exported from Setting and Monitoring tool in a text editor ...
Страница 321: ......