Chapter 9
165
Logic programming – Function blocks
Feedback error, Directional error and Fault present
Generally it is expected that the
Feedback 1/2
input always takes the inverted value
of the related
Control
input before the configured Max. switch-on feedback delay
(T
ON
) or Max. switch-off feedback delay (T
OFF
) has expired.
The
Feedback error
output becomes High, if …
the
Control
input changes from Low to High and the related
Feedback
input is Low
(irrespective of T
ON
and T
OFF
),
Or
T
ON
is greater than zero and the
Control
input changes from Low to High and the
related
Feedback
input does not change from High to Low before T
ON
has expired,
Or
T
OFF
is greater than zero and the
Control
input changes from High to Low and the
related
Feedback
input does not change from Low to High before T
OFF
has expired,
Or
Continuous monitoring when valve is active is active and the
Control
input is High
and the related
Feedback
input changes to High.
The
Directional error
output becomes High, if the Valve type parameter is =
Directional and the
Control 1
and
Control 2
inputs are High at the same time.
The
Fault present
output becomes High, if
Feedback error
and/or
Directional error
is High.
The
Feedback error
,
Directional error
and
Fault present
outputs become Low, if all
activated Control inputs are Low and all activated Feedback inputs are High. If the
Reset condition is configured as Manual reset, a valid reset pulse must be applied at
the
Reset
input additionally.
The
Min. reset pulse time
defines the minimum required duration of the pulse at the
Reset
input. Valid values are 100 ms and 350 ms. If the pulse duration is shorter than
the configured minimum pulse time or longer than 30 s, the pulse is ignored.
Ensure that the transitions of the signals for resetting fulfill the requirements of
the safety standards and regulations!
In case of a short-circuit to High (to 24 V DC) at a physical input, the evaluated signal
can have a pulse when the signal is reset due to the short-circuit detection. If such a
pulse can result in a dangerous state in the machine, the following points have to be
observed:
Ensure protected cable laying for the signal line (due to cross-circuiting to other
signal lines).
No short-circuit detection, i.e. do not reference to test outputs.
ATTENTION
Содержание SW1DNN-WS0ADR-B
Страница 2: ......
Страница 287: ...Chapter 15 284 Annex 15 Annex 15 1 Example application reports 15 1 1 Example application Newspaper palletizer ...
Страница 288: ...Chapter 15 285 Annex ...
Страница 289: ...Chapter 15 286 Annex ...
Страница 290: ...Chapter 15 287 Annex ...
Страница 291: ...Chapter 15 288 Annex ...
Страница 292: ...Chapter 15 289 Annex ...
Страница 293: ...Chapter 15 290 Annex ...
Страница 294: ...Chapter 15 291 Annex ...
Страница 295: ...Chapter 15 292 Annex ...
Страница 296: ...Chapter 15 293 Annex ...
Страница 297: ...Chapter 15 294 Annex ...
Страница 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Страница 299: ...Chapter 15 296 Annex ...
Страница 300: ...Chapter 15 297 Annex ...
Страница 301: ...Chapter 15 298 Annex ...
Страница 302: ...Chapter 15 299 Annex ...
Страница 303: ...Chapter 15 300 Annex ...
Страница 304: ...Chapter 15 301 Annex ...
Страница 305: ...Chapter 15 302 Annex ...
Страница 306: ...Chapter 15 303 Annex ...
Страница 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Страница 308: ...Chapter 15 305 Annex ...
Страница 309: ...Chapter 15 306 Annex ...
Страница 310: ...Chapter 15 307 Annex ...
Страница 311: ...Chapter 15 308 Annex ...
Страница 312: ...Chapter 15 309 Annex ...
Страница 313: ...Chapter 15 310 Annex ...
Страница 314: ...Chapter 15 311 Annex ...
Страница 316: ...Chapter 15 313 Annex 15 3 Precautions 1 Edit a CSV file exported from Setting and Monitoring tool in a text editor ...
Страница 321: ......