![Mitsubishi Electric SW1DNN-WS0ADR-B Скачать руководство пользователя страница 140](http://html.mh-extra.com/html/mitsubishi-electric/sw1dnn-ws0adr-b/sw1dnn-ws0adr-b_operating-manual_1811861140.webp)
Chapter 9
137
Logic programming – Function blocks
Inputs Up and Down
A rising edge (Low to High) at the
Up
input increases the value of the internal counter
by “1”.
A rising edge (Low to High) at the
Down
input decreases the value of the internal
counter by “1”.
If a rising edge (Low to High) occurs at the
Up
input as well as at the
Down
input
(applies only to the Up and down event counter function block), the value of the
internal counter remains unchanged.
Reset to zero
A valid pulse sequence with a Low-High-Low transition at the
Reset to zero
input sets
the internal counter to “0”. This happens irrespective of whether the
Overflow value
has been reached or not and also irrespective of whether
Reset to zero after
overflow
has been configured to
Manual
or
Automatic
.
The
Min. restart pulse time
defines the minimum required duration of the pulse at the
Reset to zero
input. Valid values are 100 ms and 350 ms. If the pulse duration is
shorter than the configured minimum pulse time or longer than 30 s, the pulse is
ignored.
Reload
A valid pulse sequence with a Low-High-Low transition at the
Reload
input sets the
internal counter to the configured value of the
Reload value
parameter. This happens
irrespective of whether
Counter reload
has been configured to
Manual
or
Automatic
.
The
Min. reload pulse time
defines the minimum required duration of the pulse at the
Reload
input. Valid values are 100 ms and 350 ms. If the pulse duration is shorter
than the configured minimum pulse time or longer than 30 s, the pulse is ignored.
Ensure that the transitions of the signals for resetting or reloading value fulfill
the requirements!
In case of a short-circuit to High (to 24 V DC) at a physical input, the evaluated signal
can have a pulse when the signal is reset due to the short-circuit detection. If such a
pulse can result in a dangerous state in the machine, the following points have to be
observed:
Ensure protected cable laying for the signal line (due to cross-circuiting to other
signal lines).
No short-circuit detection, i.e. do not reference to test outputs.
Overflow limit and Counter reset
The
Counter reset
parameter determines what happens when the counter value
reaches the
Overflow limit
. If this parameter is configured to
Automatic
, and the
internal counter equals the
Overflow limit
, the
Overflow
output becomes High for the
duration of the logic execution time. The value of the internal counter is subsequently
reset to zero.
If the
Counter reset
parameter is configured to
Manual
and the
Overflow limit
has
been reached, the
Overflow
output is set to High and remains High until the counter
value changes again, either by counting downward, by a valid
Reset to zero
pulse
sequence or by a valid pulse sequence at the
Reload
input, if the start value is smaller
than the overflow value. Until then, all further “Up” counting pulses are ignored.
ATTENTION
Содержание SW1DNN-WS0ADR-B
Страница 2: ......
Страница 287: ...Chapter 15 284 Annex 15 Annex 15 1 Example application reports 15 1 1 Example application Newspaper palletizer ...
Страница 288: ...Chapter 15 285 Annex ...
Страница 289: ...Chapter 15 286 Annex ...
Страница 290: ...Chapter 15 287 Annex ...
Страница 291: ...Chapter 15 288 Annex ...
Страница 292: ...Chapter 15 289 Annex ...
Страница 293: ...Chapter 15 290 Annex ...
Страница 294: ...Chapter 15 291 Annex ...
Страница 295: ...Chapter 15 292 Annex ...
Страница 296: ...Chapter 15 293 Annex ...
Страница 297: ...Chapter 15 294 Annex ...
Страница 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Страница 299: ...Chapter 15 296 Annex ...
Страница 300: ...Chapter 15 297 Annex ...
Страница 301: ...Chapter 15 298 Annex ...
Страница 302: ...Chapter 15 299 Annex ...
Страница 303: ...Chapter 15 300 Annex ...
Страница 304: ...Chapter 15 301 Annex ...
Страница 305: ...Chapter 15 302 Annex ...
Страница 306: ...Chapter 15 303 Annex ...
Страница 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Страница 308: ...Chapter 15 305 Annex ...
Страница 309: ...Chapter 15 306 Annex ...
Страница 310: ...Chapter 15 307 Annex ...
Страница 311: ...Chapter 15 308 Annex ...
Страница 312: ...Chapter 15 309 Annex ...
Страница 313: ...Chapter 15 310 Annex ...
Страница 314: ...Chapter 15 311 Annex ...
Страница 316: ...Chapter 15 313 Annex 15 3 Precautions 1 Edit a CSV file exported from Setting and Monitoring tool in a text editor ...
Страница 321: ......