Chapter 9
209
Logic programming – Function blocks
When an override input is configured, test pulse outputs may not be used for the
configuration of the safety inputs.
Separate lines have to be used for the sensor signals A1 and A2 (B1 and B2).
A line that is independent of other input signals has to be used for the signals for
Reset and Reset required in order to exclude unintentional resetting of the system.
The line must furthermore be laid protected.
The total muting time cannot be set to indefinite (inactive) without additional
precautions being taken. If the total muting time is set to indefinite, additional
measures have to be taken to ensure that no one can access the hazardous area
while muting is activated.
9.10.2
Parameters of the function blocks
The following table lists the possible configuration parameters of the muting function
blocks.
Parameter
Possible values
Direction detection
Disabled
Only with Parallel muting and Sequential muting:
Forward (A1/A2 first)
Backward (B1/B2 first)
Sequence monitoring
Not selectable. Defined by selection of the muting function block:
Enabled: With Sequential muting
Disabled: With Parallel muting or Cross muting
Condition of other sensor
pair for muting start
Both inputs are clear
Only with Parallel muting and Sequential muting:
If last muting sensor is active
Muting end condition
With muting sensor pair
With
ESPE
Muting total time
0 = disabled, 5 s to 3600 s, resolution 1 s
Add. muting time when
ESPE is clear
0 ms, 200 ms, 500 ms, 1000 ms
Sensor signal gap
monitoring
0 = disabled, 10 to 1000 ms, resolution 10 ms. If enabled, the
value has to be greater than the logic execution time.
Concurrency monitoring
time
0 = disabled, 10 to 3000 ms, resolution 10 ms. If enabled, the
value has to be greater than the logic execution time.
C1 input
With
Without
Conveyor input
With
Without
Override input
With
Without
Min. override pulse time
100
ms
350
ms
Table 92:
Parameters of the muting
function blocks
Содержание SW1DNN-WS0ADR-B
Страница 2: ......
Страница 287: ...Chapter 15 284 Annex 15 Annex 15 1 Example application reports 15 1 1 Example application Newspaper palletizer ...
Страница 288: ...Chapter 15 285 Annex ...
Страница 289: ...Chapter 15 286 Annex ...
Страница 290: ...Chapter 15 287 Annex ...
Страница 291: ...Chapter 15 288 Annex ...
Страница 292: ...Chapter 15 289 Annex ...
Страница 293: ...Chapter 15 290 Annex ...
Страница 294: ...Chapter 15 291 Annex ...
Страница 295: ...Chapter 15 292 Annex ...
Страница 296: ...Chapter 15 293 Annex ...
Страница 297: ...Chapter 15 294 Annex ...
Страница 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Страница 299: ...Chapter 15 296 Annex ...
Страница 300: ...Chapter 15 297 Annex ...
Страница 301: ...Chapter 15 298 Annex ...
Страница 302: ...Chapter 15 299 Annex ...
Страница 303: ...Chapter 15 300 Annex ...
Страница 304: ...Chapter 15 301 Annex ...
Страница 305: ...Chapter 15 302 Annex ...
Страница 306: ...Chapter 15 303 Annex ...
Страница 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Страница 308: ...Chapter 15 305 Annex ...
Страница 309: ...Chapter 15 306 Annex ...
Страница 310: ...Chapter 15 307 Annex ...
Страница 311: ...Chapter 15 308 Annex ...
Страница 312: ...Chapter 15 309 Annex ...
Страница 313: ...Chapter 15 310 Annex ...
Страница 314: ...Chapter 15 311 Annex ...
Страница 316: ...Chapter 15 313 Annex 15 3 Precautions 1 Edit a CSV file exported from Setting and Monitoring tool in a text editor ...
Страница 321: ......