6
PARAMETER SETTINGS
6
- 5
6.1 Parameter Settings (Board Information Settings)
(4) Operational setting
Set a network number, station number, control station/normal station and group
number of the CC-Link IE Controller Network board.
(a) Network type
Set a station type of the CC-Link IE Controller Network board.
(b) Mode
Set the operation mode of the CC-Link IE Controller Network board.
Item
Description
Max. link points per
station for LB/LW
CC IE Control (Control station)
Set as a control station of the network.
LB: 16K points
LW: 16K points
CC IE Control (Normal station)
Set as a normal station of the network.
CC IE Control Extended mode (Control station)
Set as a control station of the network.
(Extend LB/LW assignment range.)
LB: 32K points
LW:128K points
CC IE Control Extended mode (Normal station)
Set as a normal station of the network.
(Extend LB/LW assignment range.)
Select item
Description
Reference
Online
Normal operation mode
• Connects the own station to the network.
• Exchanges data with other stations.
—
Offline
Operation stop mode
• Disconnects the own station from the network.
• Does not exchange data with other stations.
—
Bus I/F test
Checks the hardware for bus I/F function of the CC-Link
IE Controller Network board.
H/W test
Checks the internal hardware of the CC-Link IE Controller
Network board.
Self-loopback test
Tests the hardware including communication circuit for
transmission system and connection cables, by a single
unit of the CC-Link IE Controller Network board.