5
PROCEDURES AND SETTINGS BEFORE OPERATION
5
- 23
5.5 Test
5.5.4 Circuit test
(4) Test mode settings
(a) Setting the executing station
Set as follows on the "Parameter setting" screen of the CC IE Control utility.
Network type: CC IE Control (Control station)
Mode: Circuit test
Station No.: Station number for the executing station
(b) Setting the target station
In the network parameter of GX Works2, set the mode to Online.
*1
*1: If the CC-Link IE Controller Network board is the target station, set as follows on the "Parameter
setting" screen of the CC IE Control utility.
Network type: CC IE Control (Normal station)
Mode: Online
Station No.: Station number for the target station
(5) Starting the test
Clicking the
button on the "Parameter setting" screen of the CC IE Control
utility displays the following confirmation dialog box.
Clicking the
button executes the circuit test.
Setting
END
Yes