6
PARAMETER SETTINGS
6
- 13
6.3 Network Range Assignment Settings
6.3.2 LX/LY settings
6.3.2
LX/LY settings
For each block, set an I/O master station and I/O ranges used in the cyclic transmission
between the I/O master and relevant stations.
(1) Setting "LX/LY settings (1)" and "LX/LY settings (2)" separately
Set "LX/LY settings (1)" as block 1 and "LX/LY settings (2)" as block 2.
POINT
• The LX/LY points for each station must be set to the maximum link points
(8192 points) or less which are total points of "LX/LY settings (1)" and
"LX/LY settings (2)".
• Avoid duplication of the LX/LY settings for each station in "LX/LY settings
(1)" and "LX/LY settings (2)".
• When a network module is set as an I/O master station, the ranges for
block 1 and block 2 should not overlap with actual I/O numbers (I/O
number range of the actually installed module) of installed CPU module.
Block 1
Link device
LX/LY setting (1)
Overlap
Actual
I/O
200
H
Overlap
5FF
H
1FFF
H
Block 2
LX/LY setting (2)
500
H
7FF
H
1FFF
H
X/Y
0
2FF
H
1FFF
H