Check code
1508
4-way valve trouble in heating mode
Abnormal points and detection methods
Causes and check points
Abnormal if 4-way valve does not operate during heating operation.
Abnormal when any of the following temperature conditions is satisfied for
3 min. or more during heating operation
1. TH22j−TH21j
[
−10°C [14
-
F]
2. TH23j−TH21j
[
−10°C [14
-
F]
3. TH22j
[
3
:
[37.4
-
F]
4. TH23j
[
3
:
[37.4
-
F]
Note:
For indoor unit, the abnormality is detected if an operating unit satisfies the
condition.
4-way valve failure
Disconnection or failure of 4-way valve coil
Clogged drain pipe
Disconnection or loose connection of connectors
Malfunction of input circuit on outdoor multi controller
circuit board
Defective outdoor power circuit board
TH21: Indoor intake temperature thermistor
TH22: Indoor liquid pipe temperature thermistor
TH23: Indoor gas pipe temperature thermistor
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Is the connector for outdoor multi
controller circuit board or 4-way valve
coil disconnected or loose?
Reconnect the connector or connect it
tightly.
Yes
Disconnect the connector for outdoor multi
controller circuit board or 4-way valve coil
to check the resistance.
No
Replace the 4-way valve.
Replace the outdoor multi controller circuit
board.
Is the detected voltage normal?
Is it free from any trace of over-heating
or burning?
Is there a resistance detected?
Check the voltage and appearance of the
outdoor multi controller circuit board.
No
No
Yes
44
OCH575