Check code
4100
Compressor current interruption (Locked compressor)
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Chart 2 of 2
Yes
Yes
No
No
Are they set properly?
Is the compressor faulty grounded?
Set the model selection switch correctly,
then restart.
Replace the compressor (Defective compressor).
Replace the outdoor power circuit board
(Defective outdoor power circuit board).
Check whether the compressor is faulty
grounded or not.
Continued from the previous page
54
OCH575