112
9-2-1.
Cross section area of Wire for Main Power and ON/OFF capacities
Model
Power Supply
Minimum Wire Cross-sectional area (mm
2
)
Breaker
for Wiring *1
Breaker for Current Leakage
Main
Cable
Branch
Ground
Outdoor
unit
P200
3N~380/400/415
V 50 Hz
2.5
–
2.5
25 A
25 A 30 mA 0.1 sec. or less
*1 A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
Total operating current
of the indoor unit
Minimum wire thickness
(mm
2
)
Ground-fault interrupter *2
Local switch (A)
Breaker for
wiring (NFB)
Main
Cable
Branch Ground
Capacity
Fuse
F0 = 16A or less *3
1.5
1.5
1.5
20 A current sensitivity *4
16
16
20
F0 = 25A or less *3
2.5
2.5
2.5
30 A current sensitivity *4
25
25
30
F0 = 32A or less *3
4.0
4.0
4.0
40 A current sensitivity *4
32
32
40
Apply to IEC61000-3-3 about max. permissive system impedance.
*2 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*3 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + {V1 × (Quantity of Others)/C}
Connect to Branch box (PAC-MK·BC)
Indoor unit
V1
V2
Type 1
SEZ-KD·VA, PCA-RP·KAQ, PLA-ZRP·BA(.UK)
19.8
2.4
Type 2
PEAD-RP·JAQ(L).UK
26.9
Type 3
MLZ-KA·VA, SLZ-KA, VAQ(L)3
9.9
Type 4
MSZ-FH·VE, MSZ-SF·VE, MSZ-EF·VE,MSZ-SF·VA, MSZ-GF·VE
6.8
Type 5
MFZ-KJ·VE
7.4
Type 6
Branch box (PAC-MK·BC)
5.1
3.0
Connect to Connection kit (PAC-LV11M)
Indoor unit
V1
V2
Type 1
MSY-EF·VE, MSY-GE·VA, MSY-GH, MSZ-GE·VA,
MSZ-SF·VA, MSZ-SF·VE, MSZ-EF·VE, MSZ-FH·VE
6.8
2.4
Type 2
MFZ-KJ·VE
7.4
Type 3
Connection kit (PAC-LV11M)
3.5
Indoor unit
V1
V2
Type 1
PMFY-VBM, PLFY-VBM, PEFY-VMS1, PCFY-VKM, PKFY-VHM,
PKFY-VKM, PFFY-VKM
19.8
2.4
Type 2
PLFY-VCM
9.9
Type 3
PKFY-VBM
3.5
Type 4
PEFY-VMA
38
1.6
Type 5
PEFY-VMHS
46.6
4.8
Type 6
PLFY-VLMD, PEFY-VMH, PEFY-VMR, PDFY-VM,
PFFY-VLEM, PFFY-VLRM
0
0
C : Multiple of tripping current at tripping time 0.01s
Please pick up “C” from the tripping characteristic of the breaker.
<Example of “F2” calculation>
Condition PLFY-VBM × 4 + PEFY-VMA × 1, C = 8 (refer to right sample chart)
F2 = 19.8 × 4/8 + 38 × 1/8
= 14.65
→
16A breaker (Tripping current = 8 × 16A at 0.01s)
*4
Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type1) + V2 × (Quantity of Type2) + V2 × (Quantity of Type3) + V2 × (Quantity of Others)
+ V3 × (Wire length[km])
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
Wire thickness
V3
1.5 mm
2
48
2.5 mm
2
56
4.0 mm
2
66
1. Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
2. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10%.
3. Specific wiring requirements should adhere to the wiring regulations of the region.
4. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57).
For example, use wiring such as YZW.
5. Install an earth longer than other cables.
6000
600
60
10
Tripping Time [s]
1
0.1
0.01
1
2
Rated Tripping current (x)
3 4
6 8
C
10
20
PUMY-P200YKM PUMY-P200YKM-BS
Sample chart
OCH575