8
4
4-1. COOLING AND HEATING CAPACITY AND CHARACTERISTICS
4-1-1. Method for obtaining system cooling and heating capacity:
To obtain the system cooling and heating capacity and the electrical characteristics of the outdoor unit, first add up the ratings
of all the indoor units connected to the outdoor unit (see table below), and then use this total to find the standard capacity with
the help of the tables on "4-3. STANDARD CAPACITY DIAGRAM".
(1) Capacity of indoor unit
4-1-2. Method for obtaining the heating and cooling capacity of an indoor unit:
(1) The capacity of each indoor unit (kW)
= the capacity
A
(or
B
)
o
(2) Sample calculation (using the system described above in 4-1-1. (2) ):
model capacity
total model capacity of all indoor units
During cooling:
During heating:
• The total model capacity of the indoor unit is:
2.8 + 5.6
o
4 = 25.2 kW
Therefore, the capacity of PKFY-P25VBM-E and
PLFY-P50VLMD-E will be calculated as follows
by using the formula in 4-1-2. (1):
Model 25 = 22.75
o
= 2.53 kW
Model 50 = 22.75
o
= 5.06 kW
• The total model capacity of indoor unit is:
3.2 + 6.3
o
4 = 28.4
Therefore, the capacity of PKFY-P25VBM-E and
PLFY-P50VLMD-E will be calculated as follows by
using the formula in 4-1-2. (1):
Model 25 = 25.19
o
= 2.84 kW
Model 50 = 25.19
o
= 5.59 kW
2.8
25.2
5.6
25.2
6.3
28.4
3.2
28.4
(2) Sample calculation
1
System assembled from indoor and outdoor unit (in this example the total capacity of the indoor units is greater than that of
the outdoor unit)
• Outdoor unit PUMY-P200YKM(-BS)
• Indoor unit PKFY-P25VBM-E
o
1 , PLFY-P50VLMD-E
o
4
2
According to the conditions in
1
, the total capacity of the indoor unit will be: 2.8 + 5.6
o
4 = 25.2
3
The following figures are obtained from the 25.2 total capacity of indoor units, referring the standard capacity diagram in
"4-3-1. PUMY-P200YKM PUMY-P200YKM-BS <cooling>" and "4-3-2. PUMY-P200YKM PUMY-P200YKM-BS <heating>" :
Model
20
Model Number
for indoor unit
Model
Capacity
2.2
Model
15
1.7
Model
25
2.8
Model
32
3.6
Model
40
4.5
Model
50
5.6
Model
63
7.1
Model
71
8.0
Model
80
9.0
Model
100
11.2
Model
125
14.0
Model
140
16.0
Model
Capacity
2.0
1.5
2.2
2.5
3.5
4.2
5.0
6.0
7.1
P
•
FY Series
M Series
Model
20
Model Number
for indoor unit
Model
15
Model
22
Model
25
Mod
35
Model
42
Model
50
Model
60
Model
71
_ _ _
_ _ _
Model
200
Model
250
22.4
28.0
_
_
_
_
DATA
Capacity (kW)
Outdoor unit power consumption (kW) Outdoor unit current (A)/400V
Cooling
Heating
Cooling
Heating
Cooling
Heating
A
22.75
B
25.19
7.04
7.01
10.92
10.88
OCH575