105
No.
SW1 setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678
1
2
3
4
5
6
7
8
52
00101
100
Outdoor LEV
-A
opening pulse
0–2000
Display of opening pulse of outdoor LEV
53
10101
100
Outdoor LEV
-A opening
pulse abnormality delay
54
01
101
100
Outdoor LEV
-A opening
pulse abnormality
55
11
101
100
Outdoor LEV
-B
opening pulse
56
0001
1100
Outdoor LEV
-B opening
pulse abnormality delay
57
1001
1100
Outdoor LEV
-B opening
pulse abnormality
58
0101
1100
63LS (Low-pressure)kgf/cm
2
−99.99–999.9
Display of data from sensor and thermistor
59
1101
1100
63LS abnormality delay
60
001
11
100
63 LS abnormality
61
101
11
100
TH2 (HIC pipe) °C
62
011111
00
TH2(HIC) abnormality delay
63
111111
00
TH2 (HIC) abnormality
64
00000010
Operational frequency
0–255
Display of actual operating frequency
65
10000010
Target frequency
0–255
Display of target frequency
66
01000010
Outdoor fan control
step number
0–15
Display of number of outdoor fan control steps (target)
69
10100010
IC1 LEV Opening pulse
0–2000
Display of opening pulse of
indoor LEV
70
01
100010
IC2 LEV Opening pulse
71
11
100010
IC3 LEV Opening pulse
72
00010010
IC4 LEV Opening pulse
73
10010010
IC5 LEV Opening pulse
74
01010010
High-pressure sensor (Pd) kgf/cm2
−99.9–999.9
Display of outdoor subcool
(SC) data and detection data
from high-pressure sensor and each thermistor
75
11010010
TH4 (Td) °C
76
001
10010
TH6 (ET) °C
77
101
10010
TH7 (Ambient-temp.) °C
78
01
110010
TH3 (Outdoor liquid pipe) °C
80
00001010
TH8 (Heat sink) °C
81
10001010
IC1
TH23 (Gas) °C
−99.9–999.9
(When indoor unit is not connected, it is displayed as"0".)
−99.9–999.9
82
01001010
IC2
TH23 (Gas) °C
83
11001010
IC3
TH23 (Gas) °C
84
00101010
IC4
TH23 (Gas) °C
85
10101010
IC5
TH23 (Gas) °C
86
01
101010
C1
TH22 (Liquid) °C
−99.9–999.9
(When the indoor unit is not connected, it is displayed as "0".)
Display of outdoor subcool (SC) data
87
11
101010
IC2
TH22 (Liquid) °C
88
0001
1010
IC3
TH22 (Liquid) °C
89
1001
1010
IC4
TH22 (Liquid) °C
90
0101
1010
IC5
TH22 (Liquid) °C
91
1101
1010
IC1
TH21 (Intake) °C
92
001
11010
IC2
TH21 (Intake) °C
93
101
11010
IC3
TH21 (Intake) °C
94
01
11
1010
IC4
TH21 (Intake) °C
95
11111
01
0
IC5
TH21 (Intake) °C
OCH575