CN2
Connect to the outdoor multi controller circuit board (CN2)
1
–
5
:
Power circuit board → Transmitting signal to the outdoor
multi controller circuit board (0–5 V DC)
2
–
5
: Zero cross signal (0–5 V DC)
3
–
4
: Not used
6
–
5
: 16 V DC
7
–
5
: 16 V DC
5
: − ,
1
,
2
,
6
,
7
:
+
[
]
100
Outdoor power circuit board
Brief Check of POWER MODULE
Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.).
If they are short-circuited, it means that they are broken.
1. Check of DIODE MODULE
L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1
2. Check of DIP-IPM
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
PUMY-P200YKM
PUMY-P200YKM-BS
Note: The marks L1 , L2 , L3 , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram are not actually printed on the board.
CN5
Detection of
primary current
(Connect to the
outdoor noise filter
circuit board (CNCT))
CN4
Connect to the outdoor multi controller
circuit board
(CN4)
W
N2
N1
P2
P1
L1
L2
L3
U
V
TAB connecter
on X52A
Connect to the
RS resistor
POWER
MODULE
TB-C1
Connect to the
smoothing capacitor
CB1 − , CB2
+
TB-P2
Connect to the smoothing
capacitor CB1
+
SC-U, SC-V,
SC-W
Connect to the
compressor (MC)
Voltage among
phases:
10–400 V AC
TB-L1, TB-L2, TB-L3
Connect to the
outdoor noise filter
circuit board
(LO1, LO2, LO3)
380 V AC
TB-N1
Connect to the
smoothing capacitor
CB2
–
and the CK
capacitor
OCH575