Check code
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards
Diagnosis
Remedy
2500
Water leakage
No
No
Yes
Is the check code
<2500> still displayed?
Replace the indoor controller board.
Note that when controller board is
defective in a usual case, the check code
<2500> is not displayed.
No abnormality
The cause might be that the drain level
was unusually high.
Restore the outdoor multi controller circuit
board, and operate the unit.
[Drain sensor]
Disconnect the connector for
drain sensor (CN31) and short-
circuit between pins 1-2 on
the indoor controller board,
then turn ON the emergency
operation switch (SWE).
[Float switch]
Disconnect the connector for
float switch (CN4F) and short-
circuit between pins 3-4 on
the indoor controller board,
then turn ON the emergency
operation switch (SWE).
Continued from the previous page
Chart 2 of 2
46
OCH575