106
No.
SW1 setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678
1
2
3
4
5
6
7
8
96
000001
10
Outdoor SC (cooling) °C
−99.9–999.9
97
100001
10
Target subcool °C
0.0–20.0
98
010001
10
IC1 SC/SH °C
−99.9–999.9
during heating: subcool (SC)/during cooling: superheat (SH)
Display of indoor SC/SH data
99
110001
10
IC2 SC/SH °C
100
001001
10
IC3 SC/SH °C
101
101001
10
IC4 SC/SH °C
102
01
1001
10
IC5 SC/SH °C
103
11
1001
10
Discharge superheat (SHd) °C
−99.9–999.9
Display of target subcool step data
105
100101
10
Target Pd display (heating) kgf/F
Pdm (0.0–30.0)
Display of all control target data
106
010101
10
Target ET
display (cooling) °C
ETm
(−2.0–23.0)
107
110101
10
Target outdoor SC (cooling) °C
SCm (0.0–20.0)
108
001
101
10
Target indoor SC/SH (IC1) °C
SCm/SHm (0.0–20.0)
109
101
101
10
Target indoor SC/SH (IC2) °C
11
0
01
1101
10
Target indoor SC/SH (IC3) °C
111
1111
011
0
Target indoor SC/SH (IC4) °C
11
2
00001
110
Target indoor SC/SH (IC5) °C
11
3
10001
110
Indoor unit check status
(No. 9 to 12 unit)
Check No.9 unit
Check
No.
10
unit
Check
No.
11
unit
Check
No.
12
unit
―
―
―
―
Same as the No.1
11
4
01001
110
Indoor unit operation mode
(No. 9 to 12 unit)
No.9 unit mode
No.10 unit mode
No.1
1 unit mode
No.12 unit mode
―
―
―
―
Cooling : light on, Heating: light blinking Stop fan: light of
f
11
5
11001
110
Indoor unit operation display (No. 9 to 12 unit)
No.9 unit operation
No.
10
unit
operat
ion
No.1
1 unit operation
No.
12
unit
operat
ion
―
―
―
―
Thermo-ON : light on Thermo-OFF: light of
f
11
6
00101
110
Indoor unit operation mode
(No.9 unit)
OFF
FA
N
Cooling thermo-ON
Cooling thermo-OFF
Heating thermo-ON
Heating thermo-ON
―
―
Display of operation mode of indoor units.
11
7
10101
110
Indoor unit operation mode
(No.10 unit)
11
8
01
101
110
Indoor unit operation mode
(No.1
1 unit)
11
9
111
0111
0
Indoor unit operation mode
(No.12 unit)
120
0001
11
10
Target
indoor SC/SH (No.
9 unit) °C
SCm/SHm (0.0–14.0) (In cooling mode, it is displayed as "0".)
Display of each cotrol target data
121
1001
11
10
Target indoor SC/SH (No.10 unit) °C
122
0101
11
10
Target indoor SC/SH (No.1
1 unit) °C
123
11
01111
0
Target indoor SC/SH (No.12 unit) °C
124
00
11111
0
Indoor LEV opening pulse at abnormality delay (No.9 unit)
0–2000
Display of opening pulse of indoor LEV at abnormality delay
125
10
11111
0
Indoor LEV opening pulse at abnormality delay (No.10 unit)
126
0111111
0
Indoor LEV opening pulse at abnormality delay (No.1
1 unit)
127
1111111
0
Indoor LEV opening pulse at abnormality delay (No.12 unit)
128
00000001
Actual frequency of abnormality delay
0–255
Display of actual frquency at time of abnormality delay
129
101
10001
Fan step number at time of
abnormality delay
0–15
Display of fan step number at time of abnormality delay
OCH575
Содержание PUMY-P200YKM
Страница 125: ...125 OCH575 ...