VII
Control ]
- 90 -
HWE10130
GB
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) The noise level is reduced by controlling the compressor frequency and outdoor fan rotation speed.
Setting of CN3D is required.(page 27)
4) Set SW3-6 to OFF (ºC setting) after servicing.
5) The refrigerant oil recovery operation can be cancelled and normal operation can be started if Stage 3 in the cooling mode or Stage
4 in the heating mode has been completed. To cancel the operation, set the SW4-7 to OFF.
Switch
Function
Function according to switch setting
Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF
ON
OFF
ON
OC
OS
SW3
1
Test run/Refrigerant oil
recovery operation En-
abled/Disabled
SW3-2, SW4-8 Dis-
abled
SW3-2, SW4-8 En-
abled
Anytime after power on
A
-
2
Test run mode: ON/
OFF
Stops all ICs
Sends a test-run
signal to all IC
After power on and when
SW3-1 is on.
A
-
3
Defrost start temper-
ature (Note 2)
-10°C [14°F]
-5°C [23°F]
Anytime after power on
B
B
4
Defrost end temper-
ature (Note 2)
10°C [50°F]
5°C [41°F]
Anytime after power on (except
during defrost operation)
B
B
5
-
-
-
-
-
-
6
Temperature unit
setting
°C
°F (Note 4)
Anytime after power on
C
C
7
-
-
-
-
-
-
8
-
-
-
-
-
-
9
Model setting
Outdoor standard
static pressure
Outdoor high static
pressure
Before being energized
C
C
10
Model setting
High static pressure
60Pa
High static pressure
30Pa
Before being energized
C
C
SW4
1
-
-
-
-
-
-
2
-
-
-
-
-
-
3
Refrigerant amount
adjustment
Normal operation
mode
Refrigerant amount
adjust mode
Anytime after being ener-
gized (except during initial
startup mode.
Automatically cancelled 60
minutes after compressor
startup)
A
-
4
Low-noise mode/
step demand switch-
ing
Low-noise mode
(Note 3)
Step demand mode Before being energized
C
C
5
-
-
-
-
-
-
6
Cumulative com-
pressor operation
time data deletion
Cumulative compres-
sor operation time
data is retained.
Cumulative compres-
sor operation time
data is deleted.
Anytime after power on
(when the unit is turned
on)
C
C
7
Refrigerant oil recov-
ery Necessary/Un-
necessary (Note 5)
Unnecessary
Necessary
Before being energized
B
B
8
Operation type
Normal control
Refrigerant oil re-
covery operation
After being energized and
when SW3-1 is set to ON
A
-
9
Refrigerant oil recovery
operation Heating/
Cooling mode selection
(Auto/Manual)
Auto (SW4-10 dis-
abled)
Manual (SW4-10
Enabled)
Any time after being ener-
gized
A
-
10
Refrigerant oil recovery
operation mode selec-
tion (Cooling/Heating)
Cooling
Heating
After being energized and
when SW4-9 is set to ON
(except during refrigerant oil
recovery operation)
A
-
Содержание PUHY-RP200
Страница 9: ...HWE10130 GB ...
Страница 11: ... 2 ...
Страница 21: ... 12 I Read Before Servicing GB HWE10130 ...
Страница 23: ... 14 ...
Страница 63: ... 54 II Restrictions GB HWE10130 ...
Страница 65: ... 56 ...
Страница 75: ... 66 ...
Страница 83: ... 74 IV Remote Controller GB HWE10130 ...
Страница 85: ... 76 ...
Страница 88: ... 79 HWE10130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Страница 97: ... 88 ...
Страница 121: ... 112 VII Control GB HWE10130 ...
Страница 123: ... 114 ...
Страница 159: ... 150 ...
Страница 259: ... 250 IX Troubleshooting GB HWE10130 ...
Страница 260: ... 251 HWE10130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 253 ...
Страница 261: ... 252 ...