IX
Troubleshooting ]
- 238 -
HWE10130
GB
[6]
Check the fan
inverter board
failure.
(1) Check the fan output wir-
ing.
Connector contact failure
Board side (CNINV)
Fan motor side
Connect the connector.
(2) Check the connector CN-
VDC connection.
Cnnector contact failure
Connect the connector.
(3) Check the FAN board
failure.
1)
The voltage imbalance among
each motor wiring during operation
(The voltage imbalance is greater
than the larger of the values repre-
sented by 5% or 5V.)
Replace the FAN board.
2)
The same error occurs even after
the operation is restarted.
Items to be checked
Phenomena
Remedy