II
Restrictions ]
- 20 -
HWE10130
GB
Reusability of Transmission line
Is the 2-core cable used?
Is the shielded wiring used?
Refer to Table A.
Fix the ground fault current.
Less than 200m
More than 0.5mm
2
Less than 130m
More than 0.3mm
2
Wiring diameter
Chart A. Centralized transmission line applicable diameter
YES
YES
NO
Please contact MITSUBISHI
ELECTRIC.
NO
YES
NO
YES
NO
YES
NO
YES
NO
NO
YES
YES
NO
Is the current in
normal state without
ground fault?
Is the farthest
transmission line between OU and
IU less than 200m?
Farthest transmission line of
centralized controller must be less
than 200m.
To find out the reusability, check the number
of indoor units, farthest length of
transmission line, and read the applicable
diameter from diagram B.
Handle the wiring that are not used
as shown in figure A.
Farthest transmission line for
centralized control system must be
less than 500m.
Is the farthest
transmission line of centralized
control system less
than 500m?
Does the diameter of the
transmission line match the
figures in Table A?
Length between power
supply unit to outdoor unit
and system controller
Shielded wiring should be connected
to the terminal at the power supply
unit side (outdoor unit).
Is the system stand-alone?
Existing transmission line can
be reused.
ࠛ
Is the diameter of
the current wiring thicker
than the diameter read
from chart A?
Change the centralized
transmission line
diameter to more than
1.25mm
2
.
Содержание PUHY-RP200
Страница 9: ...HWE10130 GB ...
Страница 11: ... 2 ...
Страница 21: ... 12 I Read Before Servicing GB HWE10130 ...
Страница 23: ... 14 ...
Страница 63: ... 54 II Restrictions GB HWE10130 ...
Страница 65: ... 56 ...
Страница 75: ... 66 ...
Страница 83: ... 74 IV Remote Controller GB HWE10130 ...
Страница 85: ... 76 ...
Страница 88: ... 79 HWE10130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Страница 97: ... 88 ...
Страница 121: ... 112 VII Control GB HWE10130 ...
Страница 123: ... 114 ...
Страница 159: ... 150 ...
Страница 259: ... 250 IX Troubleshooting GB HWE10130 ...
Страница 260: ... 251 HWE10130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 253 ...
Страница 261: ... 252 ...