VII
Control ]
- 89 -
HWE10130
GB
VII
Control
[1] Functions and Factory Settings of the Dipswitches
1. Outdoor
unit
(1) Control board
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) Refer to "VII [2] Controlling the Outdoor Unit" for details.(page 95)
Switch
Function
Function according to switch setting
Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF
ON
OFF
ON
OC
OS
SWU
1-2
Unit address setting
Set to 00 or 51-100 with the dial switch
Before power on
C
C
SW1 1-10
For self-diagnosis/
operation monitoring
Refer to the LED monitor display on the
outdoor unit board.
Anytime after power on
C
C
SW2
1
Centralized control
switch
Without connection
to the centralized
controller
With connection to
the centralized con-
troller
Before power on
B
B
2
Deletion of connec-
tion information
Normal control
Deletion
Before power on
A
-
3
Deletion of error his-
tory SW
(OC) Storage of IC/
OC error history
(OC) Deletion of IC/
OC error history
Anytime after power on
(When switched from OFF
to ON)
C
C
(OS) Storage of OS
error history
(OS) Deletion of
OS error history
4
Pump down mode
Normal control
Pump down mode
After being energized and
while the compressor is
stopped
A
-
5
-
-
-
-
-
-
6
-
-
-
-
-
-
7
Forced defrost
(Note 3)
Normal control
Forced defrost
starts
10 minutes
after com-
pressor
startup
Anytime af-
ter power
on (When
switched
from OFF to
ON)
A
A
8
Defrost timer setting
(Note 3)
50 minutes
90 minutes
Anytime after power on
(When switched from OFF
to ON)
B
B
9
-
-
-
-
-
-
10
-
-
-
-
-
-
Содержание PUHY-RP200
Страница 9: ...HWE10130 GB ...
Страница 11: ... 2 ...
Страница 21: ... 12 I Read Before Servicing GB HWE10130 ...
Страница 23: ... 14 ...
Страница 63: ... 54 II Restrictions GB HWE10130 ...
Страница 65: ... 56 ...
Страница 75: ... 66 ...
Страница 83: ... 74 IV Remote Controller GB HWE10130 ...
Страница 85: ... 76 ...
Страница 88: ... 79 HWE10130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Страница 97: ... 88 ...
Страница 121: ... 112 VII Control GB HWE10130 ...
Страница 123: ... 114 ...
Страница 159: ... 150 ...
Страница 259: ... 250 IX Troubleshooting GB HWE10130 ...
Страница 260: ... 251 HWE10130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 253 ...
Страница 261: ... 252 ...