IX
Troubleshooting ]
- 185 -
HWE10130
GB
1. Error
Code
Polarity setting error
2. Error
definition and error detection method
The error detected when transmission processor cannot distinguish the polarities of the M-NET transmission line.
3. Cause, check method and remedy
6601
Cause
Check method and remedy
(1)
No voltage is applied to the M-NET transmission line
that G(B)-50A is connected to.
Check if power is supplied to the M-NET transmission
line of the G(B)-50A, and correct any problem found.
(2)
M-NET transmission line to which G(B)-50A is con-
nected is short-circuited.