(3) Reusability check of the existing transmission lines for Replace Multi units
Check the existing wires for damage to insulation by measuring the resistance between the lead and the
ground with a 500 V ohmmeter. If the insulation resistance is less than 100 M
Ω
, replace the wires.
Check items
Notes
1. Remote controller cable (MA remote controller)
(1) Length
(2) Cable size
(3) Number of cores
(4) Cable type (shielded/unshielded)
2. Remote controller cable (ME remote controller)
(1) Length *1
(2) Cable size
(3) Number of cores
(4) Cable type (shielded/unshielded)
3. Remote controller cable (system controller)
(1) Length *1
(2) Cable size
(3) Number of cores
(4) Cable type (shielded/unshielded)
4. Indoor-outdoor transmission line
(1) Refrigerant system (Single/Multiple)
(2) Length of transmission line to the farthest unit *1
(3) Cable size
(4) Number of cores
(5) Cable type (shielded/unshielded)
(6) Number of connected indoor units
5. Centralized control transmission line
(1) Length of transmission line to the farthest unit *1
(2) Cable size
(3) Number of cores
(4) Cable type (shielded/unshielded)
7. Noise-related problems with the old units
Existing transmission lines reusability checklist
Obtain the system configuration drawing, fill out the checklist, and make a decision based on them.
Use the flowcharts on the following pages to determine the reusability of the existing transmission lines.
*1: If the remote controller (ME/System controller) length exceeds 10 m, include the exceeded length in the calculation of the
transmission line length (indoor-outdoor transmission line/centralized control system).
(5) System controller connection (Indoor unit
system/centralized control system)
6. Availability of system configuration drawing (Obtain one as
much as possible.)
8. Are there any high-frequency medical equipment in the adjacent
area that could cause noise-interference?
(Write down the nature of the problem in the “Notes” column,
if any.)
(Write down the specific nature of the concerns in the “Notes”
column, if any.)
Findings
Shielded/Unshielded
Shielded/Unshielded
Shielded/Unshielded
Indoor/Centralized
Single/Multiple
Shielded/Unshielded
Shielded/Unshielded
Available/Not available
Available/Not available
m
mm
2
m
mm
2
m
mm
2
m
mm
2
m
mm
2
Cores
Cores
Cores
Cores
units
Cores
Available/Not available
Содержание PUHY-RP200
Страница 9: ...HWE10130 GB ...
Страница 11: ... 2 ...
Страница 21: ... 12 I Read Before Servicing GB HWE10130 ...
Страница 23: ... 14 ...
Страница 63: ... 54 II Restrictions GB HWE10130 ...
Страница 65: ... 56 ...
Страница 75: ... 66 ...
Страница 83: ... 74 IV Remote Controller GB HWE10130 ...
Страница 85: ... 76 ...
Страница 88: ... 79 HWE10130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Страница 97: ... 88 ...
Страница 121: ... 112 VII Control GB HWE10130 ...
Страница 123: ... 114 ...
Страница 159: ... 150 ...
Страница 259: ... 250 IX Troubleshooting GB HWE10130 ...
Страница 260: ... 251 HWE10130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 253 ...
Страница 261: ... 252 ...