II
Restrictions ]
- 53 -
HWE10130
GB
(3) Size of the refrigerant pipe between the branches for connection to indoor units
(4) Size of the refrigerant piping between the 1st and 2nd distributor
Applicable to the RP640 model or larger
(5) Size of the refrigerant piping between the first distributor and the outdoor unit and between the second distributor
and the outdoor unit
Applicable to the RP400 model or larger
Unit: (mm) [inch]
Total capacity of the downstream units
Liquid pipe
Gas pipe
- 80
ø9.52 [3/8"]
ø15.88 [5/8"]
81 - 160
ø12.7 [1/2"]
ø19.05 [3/4"]
161 - 330
ø25.4 [1"]
331 - 630
ø15.88 [5/8"]
ø34.93 [1-3/8"]
631 -
ø19.05 [3/4"]
ø41.28 [1-5/8"]
Unit: (mm) [inch]
Liquid pipe
Gas pipe
ø19.05 [3/4"]
ø34.93 [1-3/8"]
Unit: (mm) [inch]
model
Liquid pipe
Gas pipe
RP200 model
ø9.52 [3/8"]
ø19.05 [3/4"]
RP250 model
ø22.2 [7/8"]
RP300 model
RP350 model
ø12.7 [1/2"]
ø25.4 [1"]
Содержание PUHY-RP200
Страница 9: ...HWE10130 GB ...
Страница 11: ... 2 ...
Страница 21: ... 12 I Read Before Servicing GB HWE10130 ...
Страница 23: ... 14 ...
Страница 63: ... 54 II Restrictions GB HWE10130 ...
Страница 65: ... 56 ...
Страница 75: ... 66 ...
Страница 83: ... 74 IV Remote Controller GB HWE10130 ...
Страница 85: ... 76 ...
Страница 88: ... 79 HWE10130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Страница 97: ... 88 ...
Страница 121: ... 112 VII Control GB HWE10130 ...
Страница 123: ... 114 ...
Страница 159: ... 150 ...
Страница 259: ... 250 IX Troubleshooting GB HWE10130 ...
Страница 260: ... 251 HWE10130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 253 ...
Страница 261: ... 252 ...