IX
Troubleshooting ]
- 160 -
HWE10130
GB
1. Error
Code
Drain sensor submergence (Models with a float switch)
2. Error
definition and error detection method
1) If an immersion of the float switch in the water is detected while the unit is in any mode other than the Cool/Dry mode and
when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage. While this error is being
detected, humidifier output cannot be turned on.
2) If the drain pump turns on within one hour after preliminary water leakage is detected and the above-mentioned condition is
detected two consecutive times, water leakage error water leakage is detected, and "2500" appears on the monitor.
3) Detection of water leakage is also performed while the unit is stopped.
4) Preliminary water leakage is cancelled when the following conditions are met:
One hour after the preliminary water leakage was detected, it is not detected that the drain pump goes from OFF to ON.
The operation mode is changed to Cool/Dry.
The liquid pipe temperature minus the inlet temperature is - 10°C [ -18°F] or less.
3. Cause, check method and remedy
<Reference>
2500
Cause
Check method and remedy
(1)
Drain water drainage problem
Clogged drain pump
Clogged drain piping
Backflow of drain water from other units
Check for proper drainage.
(2)
Stuck float switch
Check for slime in the moving parts of the float
switch.
Check for normal operation of the float switch.
(3)
Float switch failure
Check the resistance with the float switch turned on and
turned off.
6 minutes
6 minutes
15
seconds
15
seconds
15
seconds
15
seconds
15
seconds
ON
OFF
ON
OFF
Drain pump operation triggered by a submergence of the liquid level sensor
(except during the Cooing/Dry mode)
Drain pump
output
Float switch
input
Submergence of
the sensor
Submergence of
the sensor
Preliminary water leakage
Submergence of
the sensor
Water leakage
Sensor in the air
Sensor in the air
Within 1-hour period
Within 1-hour period
Содержание PUHY-RP200
Страница 9: ...HWE10130 GB ...
Страница 11: ... 2 ...
Страница 21: ... 12 I Read Before Servicing GB HWE10130 ...
Страница 23: ... 14 ...
Страница 63: ... 54 II Restrictions GB HWE10130 ...
Страница 65: ... 56 ...
Страница 75: ... 66 ...
Страница 83: ... 74 IV Remote Controller GB HWE10130 ...
Страница 85: ... 76 ...
Страница 88: ... 79 HWE10130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Страница 97: ... 88 ...
Страница 121: ... 112 VII Control GB HWE10130 ...
Страница 123: ... 114 ...
Страница 159: ... 150 ...
Страница 259: ... 250 IX Troubleshooting GB HWE10130 ...
Страница 260: ... 251 HWE10130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 253 ...
Страница 261: ... 252 ...