II
Restrictions ]
- 47 -
HWE10130
GB
2. Restrictions on pipe length
(1) End branching
RP200, RP250, RP300, RP350 models
1) Maximum allowable piping length depends on the total amount of refrigerant in a given system. Use the formulas below to
calculate the maximum length.
PUHY-RP200 - RP250YJM: 0.29 × L
1
+ 0.2 × L
2
+ 0.12 × L
3
+ 0.06 × L
4
+ 0.024 × L
5
< 18 (kg)
PUHY-RP300 - RP350YJM: 0.29 × L
1
+ 0.2 × L
2
+ 0.12 × L
3
+ 0.06 × L
4
+ 0.024 × L
5
< 25 (kg)
PUHY-RP200 - RP250YJM: 3.12× L
1
' + 2.15 × L
2
' + 1.29 × L
3
' + 0.65 × L
4
' + 0.26 × L
5
' < 40 [oz]
PUHY-RP300 - RP350YJM: 3.12× L
1
' + 2.15 × L
2
' + 1.29 × L
3
' + 0.65 × L
4
' + 0.26 × L
5
' < 56 [oz]
2) When merging two refrigerant piping systems into one, make sure the length difference between the two systems is 40 m [131
ft] or less.
Unit: m [ft]
Operation
Pipe sections
Allowable length of pipes
Piping
length
Total pipe length
A+B+C+D
+a+b+c+d+e+f
300 [984] or less (Note 1)
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
A+B+C+c or
A+D+f
120 [393] or less
(Equivalent length 150 [492]
or less)
Total pipe length from the first branch to the far-
thest indoor unit ( )
B+C+c or
D+f
40 [131] or less (Note 2)
Height
difference
Between indoor and
outdoor units
Outdoor unit above in-
door unit
H
50 [164] or less
Outdoor unit below in-
door unit
H'
40 [131] or less
Between indoor units
h
15 [49] or less
L
1
: Length of ø19.05 liquid pipe (m)
L
2
: Length of ø15.88 liquid pipe (m)
L
3
: Length of ø12.7 liquid pipe (m)
L
4
: Length of ø9.52 liquid pipe (m)
L
5
: Length of ø6.35 liquid pipe (m)
L
1
' : Length of ø19.05 [3/4"] liquid pipe [ft]
L
2
' : Length of ø15.88 [5/8"] liquid pipe [ft]
L
3
' : Length of ø12.7 [1/2"] liquid pipe [ft]
L
4
' : Length of ø9.52 [3/8"] liquid pipe [ft]
L
5
' : Length of ø6.35 [1/4"] liquid pipe[ft]
L
B
e
h
f
6
1
a
c
b
3
2
5
A
D
C
d
4
Branch header
Outdoor unit
H
(Outdoor unit above indoor unit)
H’
(Outdoor unit below indoor unit)
First branch
(Branch joint)
Branch joint
Indoor
Indoor
Indoor
cap
Indoor
Indoor
Indoor
Содержание PUHY-RP200
Страница 9: ...HWE10130 GB ...
Страница 11: ... 2 ...
Страница 21: ... 12 I Read Before Servicing GB HWE10130 ...
Страница 23: ... 14 ...
Страница 63: ... 54 II Restrictions GB HWE10130 ...
Страница 65: ... 56 ...
Страница 75: ... 66 ...
Страница 83: ... 74 IV Remote Controller GB HWE10130 ...
Страница 85: ... 76 ...
Страница 88: ... 79 HWE10130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Страница 97: ... 88 ...
Страница 121: ... 112 VII Control GB HWE10130 ...
Страница 123: ... 114 ...
Страница 159: ... 150 ...
Страница 259: ... 250 IX Troubleshooting GB HWE10130 ...
Страница 260: ... 251 HWE10130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 253 ...
Страница 261: ... 252 ...