VIII
Test Run Mode ]
- 120 -
HWE10130
GB
[5] Refrigerant Amount Adjust Mode
1. Procedures
Follow the procedures below to adjust refrigerant charge as necessary.
When the function switch (DIP SW5-10) on the outdoor unit MAIN board is turned to ON, the unit goes into the refrigerant
charge adjustment mode, and the following sequence is followed.
Operation
The correct amount of refrigerant will be automatically charged into the system from the cylinder that is connected
to the port.
(If refrigerant is charged in the heating mode, additional refrigerant needs to be manually added.)
1) First, operate the unit in the refrigerant charge adjustment mode for at least 45 minutes without connecting the refrigerant cyl-
inder to the unit. After confirming that the system is short on refrigerant, connect a cylinder to the system and charge the re-
frigerant. (If the operation lasts for 45 minutes or longer, the system is short on refrigerant. If refrigerant is charged from the
cylinder immediately after starting a refrigerant charge adjustment operation, refrigerant overcharge may occur.)
2) Refrigerant charge adjustment mode automatically ends in 120 minutes at the longest.
By turning off DIP SW5-10 and turning it back on, the unit will go back into the refrigerant charge adjustment mode.
3) When adjusting the refrigerant charge by using the automatic refrigerant charging function in the heating mode, the amount
of refrigerant for the field piping (except the amount for the indoor units) should be charged through the designated port, using
the automatic refrigerant charge adjustment function on the outdoor unit.
If the amount of refrigerant to be charged is unknown, operate the units in the refrigerant charge adjustment mode without
connecting the refrigerant cylinder to the system, and gradually extract the refrigerant until the units will continuously operate
for at least 45 minutes. Then, adjust the refrigerant charge, using the automatic refrigerant charge adjustment function on the
outdoor unit.
4) The table below shows the maximum allowable refrigerant charge. If the refrigerant charge adjustment mode does not end
after the amount of refrigerant designated in the table below has been charged, set Dip SW 5-10 to OFF to end the operation.
The amount of refrigerant in the table below does not include the amount for the indoor and outdoor units. Refer to Chapter
VIII [4] 3. "Amount of refrigerant to be added" for details.
Maximum refrigerant charge
Outdoor unit model
RP200
RP250
RP300
RP350
RP400
RP450
RP500
RP550
Maximum refrigerant
charge
*1
(kg)
*1. Does not include the amount for the indoor and outdoor units
18.0
18.0
25.0
25.0
25.0
25.0
25.0
25.0
Outdoor unit model
RP600
RP650
RP700
RP750
RP800
RP850
RP900
Maximum refrigerant
charge
*1
(kg)
25.0
25.0
25.0
25.0
25.0
25.0
25.0
Содержание PUHY-RP200
Страница 9: ...HWE10130 GB ...
Страница 11: ... 2 ...
Страница 21: ... 12 I Read Before Servicing GB HWE10130 ...
Страница 23: ... 14 ...
Страница 63: ... 54 II Restrictions GB HWE10130 ...
Страница 65: ... 56 ...
Страница 75: ... 66 ...
Страница 83: ... 74 IV Remote Controller GB HWE10130 ...
Страница 85: ... 76 ...
Страница 88: ... 79 HWE10130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Страница 97: ... 88 ...
Страница 121: ... 112 VII Control GB HWE10130 ...
Страница 123: ... 114 ...
Страница 159: ... 150 ...
Страница 259: ... 250 IX Troubleshooting GB HWE10130 ...
Страница 260: ... 251 HWE10130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 253 ...
Страница 261: ... 252 ...