IX
Troubleshooting ]
- 186 -
HWE10130
GB
1. Error
Code
Transmission processor hardware error
2. Error
definition and error detection method
Although "0" was surely transmitted by the transmission processor, "1" is displayed on the transmission line.
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc-
curred.
3. Cause
1) When the wiring work of or the polarity of either the indoor or outdoor transmission line is performed or is changed while the
power is on, the transmitted data will collide, the wave shape will be changed, and an error will be detected.
2) Grounding fault of the transmission line
3) When grouping the indoor units that are connected to different outdoor units, the male power supply connectors on the multiple
outdoor units are connected to the female power supply switch connector (CN40).
4) When the power supply unit for transmission lines is used in the system connected with MELANS, the male power supply
connector is connected to the female power supply switch connector (CN40) on the outdoor unit.
5) Controller failure of the source of the error
6) When the transmission data is changed due to the noise on the transmission line
7) Voltage is not applied on the transmission line for centralized control (in case of grouped indoor units connected to different
outdoor units or in case of the system connected with MELANS)
4. Check method and remedy
6602
NO
Tightly reconnect the male power
supply connector to the female
power supply switch connector (CN40).
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
Is the transmission line work
performed while the power is on?
Check the power source of the indoor unit.
198 / 264V?
Check the transmission line work is performed
and the shielded wire is treated properly.
Grounding fault or does the shielded
wire contact with the transmission line?
System ?
Faulty power source work
Improper transmission line work
Turn off the power source of outdoor/indoor
units, and turn them on again.
NO
Investigation into the
transmission line noise
Noise exist?
Controller failure of the
source of the error
*For the investigation method, follow
<Investigation method of transmission wave shape/noise>
Investigation into the
cause of the noise
Correct the error.
System with the power supply
unit for transmission lines
Is the male power supply connector
connected to the female power supply
switch connector (CN40) on only one
of the outdoor unit?
Is the male power supply connector
connected to the female power supply
switch connector (CN40) ?
Confirm that the power supply
connector on the outdoor
unit is not plugged into CN40.
Confirm that the power supply
connector on the outdoor
unit is not plugged into CN40.
Disconnect the male
power supply on
CN40 and connect it to CN41
Single-outdoor-unit system
Multiple-outdoor-unit system
Содержание PUHY-RP200
Страница 9: ...HWE10130 GB ...
Страница 11: ... 2 ...
Страница 21: ... 12 I Read Before Servicing GB HWE10130 ...
Страница 23: ... 14 ...
Страница 63: ... 54 II Restrictions GB HWE10130 ...
Страница 65: ... 56 ...
Страница 75: ... 66 ...
Страница 83: ... 74 IV Remote Controller GB HWE10130 ...
Страница 85: ... 76 ...
Страница 88: ... 79 HWE10130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... VI Refrigerant Circuit 86 HWE10130 GB ...
Страница 97: ... 88 ...
Страница 121: ... 112 VII Control GB HWE10130 ...
Страница 123: ... 114 ...
Страница 159: ... 150 ...
Страница 259: ... 250 IX Troubleshooting GB HWE10130 ...
Страница 260: ... 251 HWE10130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 253 ...
Страница 261: ... 252 ...