62
3 SPECIFICATIONS
3.3 Performance Specifications
NZ2GN12A2-16T transistor output module
*1 Make sure that the total amount of output current that flows through one connector is 4A or less.
*2 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. (
*3 For a power supply to be connected to the waterproof I/O module (such as the module-and-sensor power supply or the load power
supply and external power supply for output part), use the power supply that meets the following condition.
SELV (Safety Extra Low Voltage): Product with reinforced insulation from the hazardous potential part (60V or higher)
Item
NZ2GN12A2-16T
Station type
Remote station
Authentication Class
Authentication Class B
Network topology
Line topology, star topology, mixture of star topology and line topology, ring topology
Number of output points
16 points
Rated load voltage
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Max. load current
4A/point (Y0 to Y3)
, 2A/point (Y4 to YF), 12A/common
Maximum inrush current
Current is limited by the overload protection function.
Leakage current at OFF
0.1mA or less
Max. voltage drop at ON
0.25VDC (TYP.) 2A, 0.5VDC (MAX.) 2A, 0.5VDC (TYP.) 4A, 0.1VDC (MAX.) 4A
Output response time
OFF
ON
0.5ms or less
ON
OFF
0.8ms or less (resistive load)
Surge suppressor
Zener diode
External power supply for
output part
Voltage
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Current
25mA or less (TYP. 24VDC per common) External load current is not included.
Withstand voltage
720VDC for 1 minute between all DC external terminals and ground
Insulation resistance
10M
or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise immunity
Noise voltage 500Vp-p, noise width 1
s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
Protection degree
IP67
Wiring method for common
16 points/common (2-wire, waterproof connector type)
Sink type
Protection function
Overload protection
function
Limited current when detecting overcurrent: 9A or more/point
Activated to each point.
Overheat protection
function
Activated to each point.
External interface
Communication part
M12 waterproof connector, 8 pins, female, X-code
Module power supply part
M12 waterproof connector, 5 pins, male, female, L-code
I/O part
M12 waterproof connector, 5 pins, female, A-code
Applicable waterproof
connector
For communications
Page 148 List of Recommended Cables/Connectors for the I/O Module (Waterproof Module)
For power supply
For I/O
Y-branch connector for I/O
Multicast filter
Available
Cyclic transmission
RX/RY points
16 points
RWr/RWw points
4 points
Module power supply
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
110mA or less (24VDC, all points ON)
Weight
0.42kg