212
11 TROUBLESHOOTING
11.6 Method for Checking Error Codes
To initialize the error history, click the [Delete Error History] button.
Checking by Error code (RWr1)
Check the latest error code with the remote register of the master/local module.
Operating procedure
[Online]
[Monitor]
[Device/Buffer Memory Batch Monitor]
Ex.
When the refresh target device for Error code (RWr1) is W101
■
How to clear an error
How to clear an error depends on the error type.
■
How to clear an error using the command execution of slave station.
Follow the procedure below to clear an error using the command execution of slave station.
Operating procedure
1.
Select an I/O module from the station list on the "CC-Link IE TSN Configuration" window.
Error type
How to clear an error
Major error
An error cannot be cleared.
Moderate error
Eliminate the error cause, and power off and on the I/O module. Or, turn on and off Error clear request flag
(RWw0.b10).
Minor error
Eliminate the error cause, and power off and on the I/O module. Or, turn on and off Error clear request flag
(RWw0.b10).