3 SPECIFICATIONS
3.3 Performance Specifications
59
3
NZ2GNCF1-32T transistor output module
*1 The performance specifications vary depending on firmware versions of modules used. (
Page 256 Added and Changed Functions)
*2 Use bar solderless terminals for wiring.
*3 Only one wire can be inserted into a wire insertion opening for the terminal block for module power supply and FG. Multiple wires cannot
be connected to a terminal. Connecting two or more wires may cause a poor contact.
*4 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. (
Item
NZ2GNCF1-32T
Station type
Remote station
Authentication Class
Authentication Class B
Network topology
Line topology, star topology, mixture of star topology and line topology, ring topology
Number of output points
32 points
Rated load voltage
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Max. load current
0.1A/point, 3.2A/common
Maximum inrush current
Current is limited by the overload protection function.
Leakage current at OFF
0.1mA or less
Max. voltage drop at ON
0.1VDC (TYP.) 0.1A, 0.2VDC (MAX.) 0.1A
Output response time
OFF
ON
0.1ms or less
ON
OFF
0.8ms or less (resistive load)
Surge suppressor
Zener diode
External power supply for
output part
Voltage
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Current
40mA or less (TYP. 24VDC per common) External load current is not included.
Withstand voltage
510VAC for 1 minute between all DC external terminals and ground
Insulation resistance
10M
or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise immunity
Noise voltage 500Vp-p, noise width 1
s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
Protection degree
IP2X
Wiring method for common
32 points/common (Common terminal: pin number A1, A2) (1-wire, 40-pin connector type)
Sink type
Protection function
Overload protection
function
Limited current when detecting overcurrent: 1 to 3A/point
Activated to each point.
Overheat protection
function
Activated to each point.
External interface
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (2-piece spring clamp terminal block)
I/O part
40-pin connector
Applicable wire size
For power supply
Stranded wire: 0.3 to 1.5
(22 to 16 AWG), terminal slot size: 2.4mm
1.5mm
For I/O
40-pin connector
The size depends on the connector plug used (sold separately). (
Applicable solderless
terminal
Terminal block for module
power supply and FG
Page 127 Applicable solderless terminal
Multicast filter
Available
Cyclic transmission
RX/RY points
32 points
RWr/RWw points
4 points
Module power supply
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
120mA or less (24VDC, all points ON)
Weight
0.16kg