6 INSTALLATION AND WIRING
6.9 Wiring of I/O Module and External Device
143
6
■
For A6CON2
The following table shows the specifications of the FCN-363T-T005/H to be used for the A6CON2.
For wiring of the A6CON2, a special tool is required.
For how to use or adjust the tool, contact FUJITSU COMPONENT LIMITED.
■
For A6CON3
For wiring of the A6CON3, special tools are required.
For how to use or adjust the tools, contact FUJITSU COMPONENT LIMITED.
The following figure shows the array of terminals for flat cables. (a view from the outlet of a 40-pin connector)
5.
Place the body in one of the cover and insert the fixing
screws into the screw holes. After that, fit the other
cover on the body.
6.
Tighten the four screws.
Applicable wire size
Cross-section area of
the wire
Crimp height
Sheath outside
diameter
Stripping length
24 AWG
0.20 to 0.24
1.25 to 1.30
1.2 or less
3.0 to 4.0
26 AWG
0.13 to 0.16
1.20 to 1.25
1.2 or less
3.0 to 4.0
28 AWG
0.08 to 0.096
1.15 to 1.20
1.2 or less
3.0 to 4.0
1.
Check the terminal layout and crimp the wires to the
connector.
B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 B16 B17 B18 B19 B20
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20