216
11 TROUBLESHOOTING
11.7 Error Code List
*1 This error occurs only once when an abnormality is detected. Before clearing the error, eliminate the cause and check that a data link is
established.
*2 For these types of errors, more than one error may not occur at the same time. If errors occur, eliminate the cause of one error after
another until a data link is established.
D000H
Minor error
Communication
setting error 1
Invalid network settings are
received.
Power off and on the module power supply.
If this error occurs again, the possible cause is a module
failure.
Please consult your local Mitsubishi representative.
D001H
Minor error
Communication
setting error 2
Network settings that cannot be
handled by the I/O module are
received.
Check that the model name of the slave station set in the
network configuration settings matches the model name of
the actual device.
If this error occurs even when the model names match,
perform a firmware update so that the firmware of the I/O
module becomes the latest.
If this error occurs even with the latest firmware, the possible
cause is a module failure. Please consult your local
Mitsubishi representative.
D010H
Minor error
IP address duplication
detection
An IP address duplication is
detected.
Change the IP address so that no IP address duplication
occurs in the access range of CC-Link IE TSN. After change,
power off and on the module power supply.
D011H
Moderate
error
IP address setting
error
Values the I/O module cannot use
were set for the IP address and
subnet mask settings.
• Without using the set IP address and subnet mask, the
module is operated based on the previous IP address and
subnet mask.
• The set IP address and subnet mask will not be saved in
non-volatile memory.
• Check the IP address and subnet mask again, and change
the settings to values the I/O module can use. After
change, power off and on the module power supply.
D020H
Minor error
Network synchronous
communication
setting error
"Network Synchronous
Communication" of the I/O
module is set to "Synchronous".
• Set "Network Synchronous Communication" of the I/O
module to "Asynchronous".
• Perform a firmware update so that the firmware of the I/O
module becomes the latest.
D021H
Minor error
Number of RX/RY
points error
RX/RY with a number of points
that cannot be handled by the I/O
module are set.
Set 32 or less for the number of points for RX and RY in the
network configuration setting.
D022H
Minor error
RWr/RWw number of
points error
RWr/RWw with a number of
points that cannot be handled by
the I/O module are set.
Set 144 or less for the number of points for RWr and RWw in
the network configuration setting.
D023H
Minor error
Communication cycle
setting error (1Gbps)
When the I/O module was
operating at a communication
speed of 1Gbps, a communication
cycle the I/O module could not
support was set.
For the communication cycle setting, set a value supported
by the I/O module.
D024H
Minor error
Communication cycle
setting error
(100Mbps)
When the I/O module was
operating at a communication
speed of 100Mbps, a
communication cycle the I/O
module could not support was set.
For the communication cycle setting, set a value supported
by the I/O module.
D025H
Minor error
RWr/RWw setting
error
The system area (RWr3/RWw3) is
not set in "RWr Setting" and
"RWw Setting".
Correct the "RWr Setting" and "RWw Setting" in the network
configuration setting to assign the system area (RWr3/
RWw3).
D026H
Minor error
Synchronization cycle
setting error
The synchronization cycle set in
the master station is not
supported by the I/O module.
Correct the synchronization cycle of the master station, and
then turn off and on the power supply of the I/O module or
perform remote reset.
Error code
Error type
Error name
Description and cause
Action