174
8 FUNCTIONS
8.3 CC-Link IE TSN Network Synchronous Communication Function
Operation mode setting
Set the operation mode using the function setting switch 6 and the function setting switch 7 of the I/O module.
*1 This mode cannot be used for the I/O module with the firmware version of "04" or earlier.
*2 Do not use this combination. If it is set, a MODE switch incorrect (error code: 0107H) occurs.
The operation mode setting is determined by the combined status of function setting switches 6 and 7 when the I/O module
starts. If the status of function setting switch 6 or 7 has been changed while the I/O module is powered on, the operation mode
setting remains the same. When changing the operation mode, power off and on the module power supply or perform remote
reset.
Checking setting status
The setting status of the CC-Link IE TSN Network synchronous communication function can be checked with Function
selection status area (RWr2).
Page 233 CC-Link IE TSN Network synchronous communication setting status (RWr2.b4, RWr2.b5)
Function setting switch 6
Function setting switch 7
Operation mode
Off
Off
Synchronous X/Y control mode (factory default)
Off
On
Synchronization cycle timing control mode
On
Off
Set time synchronization control mode
On
On