208
11 TROUBLESHOOTING
11.5 Examples of Troubles with the I/O Module
When the output module is off, the LED connected as a load dimly turns on
■
Cause
The load operates by the leakage current when the output module is off.
■
Action
Connect a resistor of 5 to 50k
in parallel with the LED load.
When a digital display unit is connected as a load, data may not be displayed normally
■
Cause
The load operates by the leakage current when the output module is off.
■
Action
Install a pull-up resistor of 5 to 50k
and 0.5W between the outputs of 24VDC power supply and the output module.
LED
COM-
Y0
Output module
24VDC
power
supply
Countermeasure
Sink output
Y0
CTL+
COM-
Digital display unit
(input signal section)
Countermeasure
24VDC
power
supply
Output module
Dedicated
IC
Sink output
Содержание NZ2GN2B1-32D