11 TROUBLESHOOTING
11.7 Error Code List
215
11
0200H
Minor error
IP address/station
number setting switch
changed error
An IP address/station number
setting switch has been changed
with the module power supply on.
Return the IP address/station number setting switch to the
setting it had when the module was powered on.
0201H
Minor error
Function setting
switch 1 changed
error
The function setting switch 1 has
been changed with the module
power supply on.
Return the function setting switch 1 to the setting when the
module power supply was on.
0202H
Minor error
Function setting
switch 2 changed
error
The function setting switch 2 has
been changed with the module
power supply on.
Return the function setting switch 2 to the setting when the
module power supply was on.
0203H
Minor error
Function setting
switch 3 changed
error
The function setting switch 3 has
been changed with the module
power supply on.
Return the function setting switch 3 to the setting when the
module power supply was on.
0204H
Minor error
Function setting
switch 4 changed
error
The function setting switch 4 has
been changed with the module
power supply on.
Return the function setting switch 4 to the setting when the
module power supply was on.
0205H
Minor error
Function setting
switch 5 changed
error
The function setting switch 5 has
been changed with the module
power supply on.
Return the function setting switch 5 to the setting when the
module power supply was on.
0206H
Minor error
Function setting
switch 6 changed
error
The function setting switch 6 has
been changed with the module
power supply on.
Return the function setting switch 6 to the setting when the
module power supply was on.
0207H
Minor error
Function setting
switch 7 changed
error
The function setting switch 7 has
been changed with the module
power supply on.
Return the function setting switch 7 to the setting when the
module power supply was on.
0208H
Minor error
Function setting
switch 8 changed
error
The function setting switch 8 has
been changed with the module
power supply on.
Return the function setting switch 8 to the setting when the
module power supply was on.
0209H
Minor error
Function setting
switch 9 changed
error
The function setting switch 9 has
been changed with the module
power supply on.
Return the function setting switch 9 to the setting when the
module power supply was on.
020AH
Minor error
Function setting
switch 10 changed
error
The function setting switch 10 has
been changed with the module
power supply on.
Return the function setting switch 10 to the setting when the
module power supply was on.
0210H
Minor error
Output change
disabled time setting
error
A time with which the output
change becomes disabled has
been set for Output time setting
Y
while the I/O module is
operating in the set time
synchronization control mode.
The output cannot be changed because the period from the
setting done to the set time is too short. Set a time same as
or later than the start timing of the second synchronization
cycle from the setting.
0220H
Minor error
Error history save limit
error
The upper limit for the number of
times an error is saved in the error
history is reached.
No more errors can be saved in the error history. Check the
error by the latest error code.
0221H
Minor error
IP address save limit
error
The upper limit for the number of
times the IP address is changed
is reached.
An IP address change made when and after this error
occurred is not saved into the non-volatile memory.
0240H
Minor error
Module power supply
voltage drop error
The module power supply voltage
is dropped.
• Check the state of the module power supply.
• Check if the power supply voltage satisfies the
specifications for the I/O module.
0250H
Minor error
Non-volatile memory
access error (IP
address)
The IP address cannot be saved
because an error in access to the
non-volatile memory was
detected.
• The IP address is not saved into the non-volatile memory.
• Take measures against noise with a shielded cable for
connection.
• If this error occurs again, the possible cause is a module
failure. Please consult your local Mitsubishi representative.
0251H
Minor error
Non-volatile memory
access error (error
history)
The error cannot be saved
because an error in access to the
non-volatile memory was
detected.
• An error that occurred at the time of or before this error
may not be saved into the non-volatile memory.
• Take measures against noise with a shielded cable for
connection.
• If this error occurs again, the possible cause is a module
failure. Please consult your local Mitsubishi representative.
0270H
Minor error
Remote reset disable
error
Remote reset could not be
performed because the setting of
the NETWORK switch or the LINK
SPEED switch is different from
the setting it had when the
module was powered on.
Return the NETWORK switch and LINK SPEED switch to the
settings they had when the module was powered on, and
then perform remote reset again.
Error code
Error type
Error name
Description and cause
Action