15 - 6
15 EMC DIRECTIVES
(3) Cable clamp
It is also possible to ground the exposed shielded part of the cable to the panel
with the cable clamp.
• Ground the shield at a position 20 to 30cm (7.87 to 11.81 inch) away from the
module.
• When the cables pulled out from the control panel, ground the cables at a
position 5 to 10cm (1.97 to 3.94inch) near the input/output hole of the control
panel with the cable clamp.
AD75CK
AD75CK
Inside control panel
Motion controller
5 to 10cm
(1.97 to 3.94 inch)
20 to 30cm
(7.87 to 11.81 inch)
• Cable clamp (Recommended product)
Manufacturer Model
name
AERSBAN-DSET
AERSBAN-ESET
Mitsubishi electric
AD75CK