6 - 22
6 INSPECTION AND MAINTENANCE
(h) Flowchart for when servo amplifier does not start
The following shows the flowchart for when servo amplifier does not start.
Servo amplifier does not start.
Is there error display
on 7-segment LED of Motion
controller?
Remove the error cause.
YES
NO
NO
YES
Does servo amplifier start?
Has
the control power supply
of servo amplifier
turn on?
the control power supply of servo
amplifier turn on.
YES
YES
NO
NO
Is the connection of
SSCNET cable correct?
END
Explain the error symptom and get
advice from out sales representative.
YES
NO
NO
Connect the SSCNET cable correctly.
Is the axis select
rotary switch of servo amplifier
correct?
NO
Set the axis select rotary switch in "0",
turn on the power supply of the
servo amplifier.
YES
NO
YES
YES
Does servo amplifier start?
Does servo amplifier start?
Does servo amplifier start?