3. STARTUP
3 - 2
3.2 IP address setting
POINT
Use a twisted pair cable with Ethernet Category 5e (1000BASE-T) or higher as
an Ethernet cable. The maximum cable length between nodes is 100 m.
Use a hub with a transmission speed of 100 Mbps or faster when branching the
Ethernet communication using a switching hub.
For the switching hub without the auto-negotiation function, set it to the
transmission speed 100 Mbps and half duplex.
The initial value of the IP address is 192.168.3.0.
The 4th octet can be set to 1 to 255 by using the identification number setting
rotary switch (SW1/SW2).
Cycle the power of the servo amplifier after changing the parameter setting of
the IP address or identification number setting rotary switch (SW1/SW2).
The IP address range for Modbus/TCP communication is between 0.0.0.0 and
255.255.255.255. Set the IP address within the range.
Set the IP address with the identification number setting rotary switch (SW1/SW2) on the display of the servo
amplifier or MR Configurator2.
When the IP address is changed with the identification number setting rotary switch (SW1/SW2), change it
before powering on the servo amplifier.
The IP address you set can be checked in the system configuration window of MR Configurator 2.
The IP address can be set as follows.
Identification number setting
rotary switch (SW1/SW2)
IP address
00h
1st octet
The setting value of [Pr. PN11] is used.
2nd octet
The setting value of [Pr. PN12] is used.
3rd octet
The setting value of [Pr. PN13] is used.
4th octet
The setting value of [Pr. PN14] is used.
01h to FFh
1st octet
The setting value of [Pr. PN11] is used.
2nd octet
The setting value of [Pr. PN12] is used.
3rd octet
The setting value of [Pr. PN13] is used.
4th octet
The setting value of the identification number setting rotary switch
(SW1/SW2) is used.