31
BCN-B11127-479*
(2) Detail list
Class
No
Symbo
l
Name and function
Initial
Value
Unit Setting
Rnge
0
*STY Control mode, Regenerative brake option selection
Use to select regenerative brake option.
0
0
0000
0000h
to
0710h
1
*FTY Feeding system selection
Used to set the feed length multiplication factor and
External pulse multiplication factor.
0
0000 0000h
to
1013h
B
a
s
ic
param
et
ers
2
*OP1 Function selection 1
Used to select the input filter and absolute position detection system.
0 0
0002 0000h
to
1006h
Selection of regenerative brake option
0: Not used
1: Spare (do not set)
2: MR-RB032
3: MR-RB12
4: MR-RB32
5: MR-RB30
6: MR-RB50
7: Spare (do not set)
ST1 coordinate system selection
0: Address is incremented in CCW direction
1: Address is incremented in CW direction
Feed length multiplication factor (STM)
0: 1 time
1: 10 times
2: 100 times
3: 1000 times
SON-off, EMG-off follow-up for absolute value
Command in incremental system
0: Invalid
1: Valid
Selection of command mode
0: Absolute value command
1: Incremental value command
Input filter
If external input signal causes chattering due
To noise, etc., input filter is used to suppress
it.
0: None
1: 0.888msec
2: 1.777msec
3: 2.666msec
4: 3.555msec
5: 4.444msec
6: 5.333msec
Selection of absolute position detection system
0: Incremental system
1: Absolute position detection system