3.5 Additional function devices
By parameter setting, you can assign the signals given in this section to the pins of connectors CN1A and
CN1B, in addition to the signals in Section 3.2.
(1) Pins which accept different signals
Pin Type
Connector Pin No.
Device in Initial Status
Device Symbol
CN1B-5
Point table No. selection 1
DI0
CN1B-14
Point table No. selection 2
DI1
CN1A-8 Proximity
dog
DOG
CN1B-15 Servo
on
SON
CN1B-16
Forward rotation stroke end
LSP
CN1B-17
Reverse rotation stroke end
LSN
CN1B-7 Automatic/manual
selection
MDO
CN1B-8
Forward rotation start
ST1
Input-only pins
CN1B-9
Reverse rotation start
ST2
I/O pin
CN1A-19
Empty
CN1B-4 Rough
match
CPO
CN1B-6 In
position
INP
CN1B-18 Trouble
ALM
CN1B-19 Ready
RD
Output-only pins
CN1A-18 Zeroing
completion
ZP
(2) Assignable devices
1) Input devices
Device Name
Symbol
Description
I/O Division
No assigned function
No function is assigned.
Emergency stop
EMG When EMG-SG are opened, the servo amplifier is placed in the emergency
stop status, the servo switches off, and the dynamic brake is operated to bring
the servo motor to a sudden stop.
Short EMG-SG in the emergency stop status to cancel the emergency stop
status.
DI-1
Alarm reset
RES Short RES-SG to deactivate the alarm.
If RES-SG are shorted in no alarm status, the base circuit is not shut off.
Set 0 in parameter No. 55 to shut off the base circuit.
Some alarms cannot be deactivated by the reset signal.
Since this device is not designed for stopping, do not switch it on during
operation.
DI-1
Point table No. selection
DI2
DI3
DI4
Valid in the automatic mode.
The following table lists the point table numbers that may be chosen by the
combinations of DI0, DI1, DI2, DI3 and DI4:
DI4 DI3 DI2 DI1 DI0 Selected
point
table
No.
0 0 0 0 0
Zeroing
operation
0 0 0 0 1
Point
table
No.1
0 0 0 1 0
Point
table
No.2
0 0 0 1 1
Point
table
No.3
: : : : :
:
1 1 1 0 1
Point
table
No.28
1 1 1 0 1
Point
table
No.29
1 1 1 1 0
Point
table
No.30
1 1 1 1 1
Point
table
No.31
Note:0: DI3/DI2/DI1/DI0-SG open
1: DI3/DI2/DI1/DI0-SG shorted
DI-1
External torque limit
selection
TL0
Short TL0-SG to make external analog torque limit valid.
DI-1
Internal torque limit
selection
TL1
Open TL1-SG to make the torque limit value set in parameter No.28 (TL1)
valid, or short them to make the value set in parameter No.29 (TL2) valid.
DI-1