122
Table 6.3 Error Code List for AnUCPU (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
"FUSE
BREAK
OFF"
(Checked
continuousl
y.)
32
Stop or
Continu
e (set
by
parame
ter)
(1) There is an output
module of which
fuse is blown.
(2) The external power
supply for output
load is turned OFF
or is not connected.
(1) Check the FUSE
BLOWN indicator
LED on the output
module and replace
the fuse.
(2) Read detailed error
code using a
peripheral device and
replace the fuse of
the output module
which corresponds to
the data (I/O head
number).
Or, monitor special
registers D9100 to
D9107 using a
peripheral device and
replace the fuse of
the output module of
which corresponding
data bit is "1".
(3) Check the ON/OFF
status of the external
power supply for
output load.