127
Table 6.3 Error Code List for AnUCPU (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
0 [When
using
MELSECNET/(II)]
(1) When the link range
at a data link CPU
which is also a
master station
(station number =
00) is set by
parameter setting at
a peripheral device,
for some reason the
data written to the
link parameter area
differs from the link
parameter data read
by the CPU.
Alternatively, no link
parameters have
been written.
(2) The total number of
slave stations is set
at 0.
(1) Write the parameters
again and check.
(2) Check the station
number settings.
(3) Persistent error
occurrence may
indicate a hardware
fault. Consult your
nearest Mitsubishi
representative,
explaining the nature
of the problem.
"LINK
PARA.
ERROR"
47
470*
Continu
e
[When using
MELSECNET/10]
(1) The contents of the
network refresh
parameters written
from a peripheral
device differ from
the actual system at
the base unit.
(2) The network refresh
parameters have
not been written.
Write the network
refresh parameters
again and check.
Содержание Melsec A Series
Страница 90: ...77 MEMO ...
Страница 149: ......