130
Table 6.3 Error Code List for AnUCPU (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
475* [When
using
MELSECNET/10]
(1) The contents of the
network parameters
for the third link unit,
written from a
peripheral device,
differ from the actual
network system.
(2) The link parameters
for the third link unit
have not been
written.
(3) The setting for the
total number of
stations is 0.
476* [When
using
MELSECNET/10]
(1) The contents of the
network parameters
for the fourth link
unit, written from a
peripheral device,
differ from the actual
network system.
(2) The link parameters
for the fourth link unit
have not been
written.
(3) The setting for the
total number of
stations is 0.
(1) Write the parameters
again and check.
(2) Check the station
number settings.
(3) Persistent error
occurrence may
indicate a hardware
fault. Consult your
nearest Mitsubishi
representative,
explaining the nature
of the problem.
"LINK
PARA.
ERROR"
47
477
Continu
e
A ink parameter error
was detected by the
CC-Link module.
(1) Write the parameters
in again and check.
(2) If the error appears
again, there is a
problem with the
hardware.
Consult your nearest
System Service, sales
office or branch office.
Содержание Melsec A Series
Страница 90: ...77 MEMO ...
Страница 149: ......