134
Table 6.3 Error Code List for AnUCPU (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
(1) The CPU
malfunctioned due
to noise.
(2) Hardware failure.
(1) Take proper
countermeasures for
noise.
(2) Hardware failure.
"MAIN CPU
DOWN"
60
602
STOP
(1) Failure in the power
module, CPU
module, main base
unit or expansion
cable is detected.
(1) Replace the power
module, CPU
module, main base
unit or expansion
cable.
"BATTERY
ERROR"
(Checked
at power
on.)
70
Continu
e
(1) Battery voltage has
lowered below
specified level.
(2) Battery lead
connector is not
connected.
(1) Replace battery.
(2) If a RAM memory or
power failure
compensation
function is used,
connect the lead
connector.
7. TRANSPORTATION PRECAUTIONS
When transporting lithium batteries, make sure to treat them based on the transport
regulations.
7.1 Controlled Models
The battery for AnNCPU, AnACPU and AnUCPU is classified as follows:
Product Name
Model
Product supply status
Classification for transportation
A series battery
A6BAT
Lithium battery
Non-dangerous goods
7.2 Transport Guidelines
Comply with IATA Dangerous Goods Regulations, IMDG code and the local
transport regulations when transporting products after unpacking or repacking,
while Mitsubishi ships products with packages to comply with the transport
regulations.
Also, contact the transporters.