129
Table 6.3 Error Code List for AnUCPU
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
473* [When
using
MELSECNET/10]
(1) The contents of the
network parameters
for the first link unit,
written from a
peripheral device,
differ from the actual
network system.
(2) The link parameters
for the first link unit
have not been
written.
(3) The setting for the
total number of
stations is 0.
"LINK
PARA.
ERROR"
47
474*
Continu
e
[When using
MELSECNET/10]
(1) The contents of the
network parameters
for the second link
unit, written from a
peripheral device,
differ from the actual
network system.
(2) The link parameters
for the second link
unit have not been
written.
(3) The setting for the
total number of
stations is 0.
(1) Write the parameters
again and check.
(2) Check the station
number settings.
(3) Persistent error
occurrence may
indicate a hardware
fault. Consult your
nearest Mitsubishi
representative,
explaining the nature
of the problem.