4.3.3 Power Supply Connection
Observe the following precautions for power supply wiring.
(1) Provide separate wiring systems for the PC power, I/O devices, and
operating devices as shown below.
If the wiring is influenced by excessive noise, connect an isolation
transformer.
PC
PC power
supply
Main power supply
I/O power supply
Main circuit devices
I/O devices
Main circuit devices
Isolation
transformer
200 VAC
T1
REMARK
As safety measures, install a switch for use with "online I/O module change"
only to each of the corresponding modules and equipment.
(2) Do not supply 24VDC power from more than one power supply modules in
parallel to one I/O module. If they are connected in parallel, the power
supply modules may fail.
If the 24VDC output capacity is insufficient for one power supply module,
supply 24VDC from the external 24VDC power supply as shown below:
I/O
mo
dul
e
24 VDC
24 VDC
Po
we
r s
upp
ly
m
o
dul
e
24 VDC
External power supply
Po
we
r s
upp
ly
m
o
dul
e
I/O
mo
dul
e
Po
we
r s
upp
ly
m
o
dul
e
(3) 100VAC, 200VAC, and 24VDC wires should be twisted as tightly as
possible, and connect the modules at the shortest distance between them.
To minimize voltage drop, use thick wires (MAX. 2mm
2
) where possible.
Содержание Melsec A Series