48
When setting parameters, refer to the instruction manual (applied) and understand instructions.
You can use the setting dial of the operation panel like a
potentiometer to perform operation.
The key operation of the operation panel can be disabled.
When setting a frequency using the setting dial on the operation
panel, the frequency change increment is determined by how
quickly the setting dial is rotated.
Use these parameters to select/change the input terminal
functions.
When
Pr. 59 Remote function selection
"0", the functions of the RL, RM
and RH signals are changed as given in the table.
The OH signal turns ON when the relay contact "opens".
161, 295
Operation selection of the operation
panel
Pr.161 Frequency setting/key lock operation selection
Pr.295 Magnitude of frequency change setting
Pr.161
setting
Description
0
(initial value)
Setting dial frequency setting mode
Key lock mode in valid
1
Setting dial potentiometer mode
10
Setting dial frequency setting mode
Key lock mode valid
11
Setting dial potentiometer mode
162, 165
Refer to the section about
Pr.57
166 ,167
Refer to the section about
Pr.150
168, 169
Parameter for manufacturer setting. Do not set.
170, 171
Refer to the section about
Pr.52
178 to 182
Function assignment of input terminal
Pr.178 STF terminal function selection
Pr.179 STR terminal function selection
Pr.180 AU terminal function selection
Pr.181 RM terminal function selection
Pr.182 RH terminal function selection
Pr.178
to
Pr.182
setting
Signal
Name
Function
0
RL
Pr.59
=0 (initial value)
Low-speed operation
command
Pr.59
Remote setting (setting
clear)
1
RM
Pr.59
=0 (initial value)
Middle-speed operation
command
Pr.59
Remote setting
(deceleration)
2
RH
Pr.59
=0 (initial value)
High-speed operation
command
Pr.59
Remote setting
(acceleration)
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
7
OH
External thermal relay input
8
REX
15-speed selection (combination with three
speeds RL, RM, RH)
10
X10
Inverter run enable signal (FR-HC2, FR-CV
connection)
12
X12
PU operation external interlock
14
X14
PID control valid terminal
16
X16
PU/External operation switchover (turning ON
X16 selects External operation)
24
MRS
Output stop
25
STOP
Start self-holding selection
60
STF
Forward rotation command (assigned to STF
terminal
(Pr. 178)
only)
61
STR
Reverse rotation command (assigned to STR
terminal
(Pr. 179)
only)
62
RES
Inverter reset
64
X64
Starting frequency for elevator mode
65
X65
PU/NET operation switchover
66
X66
External/NET operation switchover
67
X67
Command source switchover
72
X72
PWM frequency selection
9999
No function
Содержание F720PJ-11KF
Страница 88: ...88 MEMO ...