Standard Specifications
Three-phase 200V power supply
Three-phase 400V power supply
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor. To use a dedicated IPM motor,
refer to
.
The rated output capacity assumes the following output voltages: 220V for the three-phase 200V and 440V for the three-phase 400V class.
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100% load.
The maximum output voltage does not exceed the power supply voltage.The maximum output voltage can be changed within the setting range. However,
the pulse voltage value of the inverter output side voltage remains unchanged at about
that of the power supply.
The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
Open type (IP00) for Filterpack.
The values in parentheses are calculated with 1 fundamental frequency power factor according to the Year 2013 Standard specification for public
constructions (electric installation works), published by the Ministry of Land, Infrastructure, Transport and Tourism in Japan.
The indicated leakage current is equivalent to one-phase of the three-phase three wire
connection cable.
Rating
Inverter
Model FR-F720PJ-
K
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Applicable general-purpose motor capacity
(kW)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Outpu
t
Rated capacity (kVA)
1.0
1.6 2.7
3.8
6.3
9.1
12.1
17.1
22.1
Rated current (A)
2.5
4.2
7.0
10.0
16.5
23.8
31.8
45
58
Overload current rating
120% 60s, 150% 0.5s (inverse-time characteristics)
Rated voltage
Three-phase 200 to 240V
Po
wer
su
pp
ly
Rated input AC voltage/frequency
Three-phase 200 to 240V 50Hz/60Hz
Permissible AC voltage fluctuation
170 to 264V 50Hz/60Hz
Permissible frequency fluctuation
±5%
Power supply
capacity (kVA)
Without Filterpack
1.2
2.1
4.0
5.0
8.8
12.0
17.0
20.0
27.0
With Filterpack
0.8
1.2
2.6
3.4
5.5
8.4
11.0
16.0
19.0
Protective structure (JEM 1030)
Enclosed type (IP20)
Cooling system
Self-cooling
Forced air cooling
Approximate mass(kg)
0.8
1.0
1.4
1.4
1.8
3.6
3.6
6.5
6.5
Filterpack
Model FR-BFP2-
K
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Approximate mass(kg)
1.3
1.4
2.0
2.2
2.8
3.8
4.5
6.7
7.0
Power factor improving reactor
Install the DC reactor in the DC side. 93% to 95% of power supply power factor under 100%
load (94.4%
EMC filter
Common mode choke
Install a ferrite core on the input side
Capacitive filter
About 4mA of capacitor leakage current
Protective structure (JEM 1030)
Open type (IP00)
Inverter
Model FR-F740PJ-
K
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Applicable general-purpose motor capacity
(kW)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Outpu
t
Rated capacity (kVA)
0.9
1.7
2.8
3.8
6.2
9.1
12.4
17.5
22.5
Rated current (A)
1.2
2.2
3.7
5.0
8.1
12.0
16.3
23.0
29.5
Overload current rating
120%60s, 150% 0.5s (inverse-time characteristics)
Rated voltage
Three-phase 380 to 480V
Po
w
er
s
upply
Rated input AC voltage/frequency
Three-phase 380 to 480V 50Hz/60Hz
Permissible AC voltage fluctuation
325 to 528V 50Hz/60Hz
Permissible frequency fluctuation
±5%
Power supply
capacity (kVA)
Without Filterpack
1.1
2.2
4.2
4.8
8.6
12.0
17.0
20.0
28.0
With Filterpack
0.7
1.3
2.7
3.3
5.4
8.5
11.0
16.0
19.0
Protective structure (JEM 1030)
Enclosed type (IP20)
Cooling system
Self-cooling
Forced air cooling
Approximate mass (kg)
1.3
1.3
1.4
1.5
1.5
3.3
3.3
6.0
6.0
Filterpack
Model FR-BFP2-H
K
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Approximate mass (kg)
1.6
1.7
1.9
2.3
2.6
4.5
5.0
7.0
8.2
Power factor improving reactor
Install the DC reactor in the DC side. 93% to 95% of power supply power factor under 100%
load (94.4%
EMC filter
Common mode choke
Install a ferrite core on the input side
Capacitive filter
About 8mA of capacitor leakage current
Protective structure (JEM 1030)
Open type (IP00)
2